H B X C P U - 0 6 0 0 C o n t r o l
V e r s i o n 1 . 0 . 0
Page 15
WI-FI –
Indicates that the control is connected to a
2.4 GHz Wi-Fi network.
BOILER –
Indicates the boiler temperature and
target. If there is a demand for heating the box will
be bordered with a red outline, and the staging
output(s) in the lower wiring chamber will be
closed.
SYSTEM –
Indicates the system temperature and
target. When in boiler protection the box will have
a yellow outline.
OUTDOOR –
The outdoor temperature will be
displayed. This option will also display if the control
is in WWSD (Warm Weather Shutdown).
DHW TANK –
It will display the DHW temperature
and target. If there is a demand for DHW the zone
will be bordered with a red outline.
STAGES –
Indicates how many boilers are being
utilized in your system setup. When a boiler is
activated by a heat demand the boiler will light up
in respect to their classification.
MODULATING STAGES-
Indicates how many
modulating boilers are being utilized in your system
setup. When a modulating boiler is activated by a
heat demand the modulating boiler percentage
will start at the minimum mod percentage (%).
When there is no demand (off) the modulating
percentage (%) will displayed as 0%.
PUMPS/VALVE –
When a pump/valve is activated
by a call you will see pump (P1) ,(P2), (P3) light up
in respect to their classification, their associated
contacts PUMP 1, PUMP 2, PUMP 3 can be found in
the lower wiring chamber will be closed.
DEMANDS -
When the delegated demand is active
it will light up (DEMAND 1 - HD) or (DEMAND 2 –
DHW/SETPOINT) thus in turn the associated demand
in the upper wiring chamber will be closed.
MIXING MODE: MAIN SCREEN
1
2
3
4
5
6
7
8
9
Accessing the menu of the CPU-0600 is done by pressing the menu button (3
lines) in the top right corner.