H B X C P U - 0 6 0 0 C o n t r o l
V e r s i o n 1 . 0 . 0
Page 33
MANUAL OVERRIDE 1 –
This setting is used to put Pump
1 in manual override. When set to yes, the pump relay
is permanently on.
(ON/OFF)
MANUAL OVERRIDE 2 –
This setting is used to put Pump
2 in manual override. When set to yes, the pump relay
is permanently on.
(ON/OFF)
SEQUENCE TIME –
This setting is used to set the rotation
for the pumps based off of runtime in hours. This means
that the pump will rotate when the pump exceeds the
runtime hours inputted.
(OFF/1 to 240H)
SEQUENCE CYCLES –
This setting is used to set the
number of demands that are given before the pumps
will rotate. One cycle is described as the pump going
on and then off.
(OFF/1 to 240 Cycles)
WARM WEATHER SHUTDOWN –
This setting is used to
set the temperature in which the CPU-0600 will go
into WWSD. If the system rises above this temperature,
the system will be shut off. In WWSD the boiler and all
pumps will shut off.
(32F to 150°F)
PERMANENT DEMAND –
This will allow for a permanent
demand to control. This can be used instead of
installing a thermostat or dry contact switch.
(ON/OFF)
PERMANENT FLOW DEMAND –
This will allow for a
permanent flow demand. This can be used instead of
installing a flow switch.
(ON/OFF)
PUMP SEQUENCER MODE: PUMP SEQUENCER SETUP
Use caution. Sequence Time and Sequence Cycles will override each other.
Use only one or the other