OUTDOOR RESET
– This is used in the outdoor reset
design calculation. This option should be set to reflect
your specific city or region. (OFF/-40°F to 127°F)
BOILER SETPOINT
– When a heat demand is present
and the control is not in WWSD, the control will target
this temperature for heating. (OFF/2°F to 210°F)
MAX BOILER TEMP
– This is used in the outdoor reset
design calculation, and also serves as the maximum
setting for the boiler. This is the maximum boiler
temperature for the coldest day. (OFF/2°F to 210°F)
MIN BOILER TEMP
: This is the minimum boiler
temperature. Set this to the temperature you would
like the boiler to be when the outdoor temperature
approaches WWSD. (OFF/2°F to 210°F)
USE WEB OUTDOOR TEMP
: This setting can be used for
outdoor temperature reading via the web instead
of installing an outdoor sensor. The control must be
connected to a Wi-Fi network and the user must set
the controller to a building via the Sensorlinx mobile
app for this setting to work. (ON/OFF)
WARM WEATHER SHUTDOWN (WWSD)
: This setting is
used to set the temperature in which the CPU-0600
will go into WWSD. If the system rises above this
temperature, the system will be shut off. In WWSD the
boilers and all pumps will shut off.
(35°F to 120°F) Default: 70°F
WWSD TIME
: This setting is used as a lag time for
WWSD. This will hold the control from entering WWSD
until this time has elapsed. The timer starts when the
outdoor temperature hits WWSD. This setting is useful
in the shoulder seasons when there are large outdoor
temperature swings.
(0°F to 240°F) Default 0°F
STAGING MODE: DESIGN TEMPERATURES
This option will appear when outdoor reset is set to OFF