H B X C P U - 0 6 0 0 C o n t r o l
V e r s i o n 1 . 0 . 0
Page 27
ON DIFFERENTIAL
– Use this setting to set the differential
between setpoint 1’s temperature and setpoint 2’s
temperature. When the differential exceeds its target
for heating or cooling it will activate the pump.
(1°F to 50°F)
Ex in heating.
Differential set for 10°F. The heating pump will activate
when the differential is above 10°F.
OFF DIFFERENTIAL
– Use this setting to set when you
would like the differential to turn off.
(1°F to 50°F)
Ex in heating.
Differential set for 6°F. The heating pump will shut off
when the differential goes below 6°F.
MODULATING TIME
– This setting sets the time
between each step of the 0-10VDC output when the
modulating output needs to increase or decrease.
(1S to 240S)
MIN MOD PERCENT
– This setting is used to set the
lowest modulation level the modulating output can
go down to. It can also be used to set the minimum
position on valves.
(1% to 99%)
PERMANENT DEMAND
– This setting will allow for a
permanent heating demand.
(OFF/ON)
DIFFERENTIAL SETPOINT MODE: DIFFERENTIAL SETUP