H B X C P U - 0 6 0 0 C o n t r o l
V e r s i o n 1 . 0 . 0
Page 5
CPU-0600 INSTALLATION
CONTROL MODE
The CPU-0600 is designed to be wall mounted or installed in a separate electrical enclosure. The unit should be
installed inside and protected from falling water and high humidity conditions. With all the covers in place, it is
designed to protect any individual from accidental electrical shock. It is not suitable for installation in hazardous
locations and should not be close to any electromagnetic fields.
• Identify the four mounting holes on the CPU-0600, mark on the wall the desired location of mounting
• Pre-drill, anchor and fasten four screws for mounting
• Hang CPU-0600 and fasten tight to desired locations
• Complete wiring connections in accordance with terminal locations
The programming instructions for the CPU-0600
are broken down into the five control modes listed
below. When the control is first plugged in you are
asked to select which control mode you would like
your CPU-0600 to operate in.
STAGING MODE (DEFAULT) –
Programming for this
mode can be found on pages 6 through 14. This
mode is used when running boilers only. The boiler
configurations available in this mode are three
(3) modulating, On/Off boiler, two (2) stage On/
Off boiler, three (3) stage On/Off boiler and four
(4) On/Off boiler. Staging expandability is possible
with additional CPU-0600 controllers. In this mode
the control is able to control DHW and operate a
boiler, system, and DHW pump(s).
MIXING MODE –
Programming for this mode can be found on pages 15 through 24. This mode is used when
running mixing pumps or valves. Mixing configurations include PMIp, Modulating, and Floating Action Valve. In
this mode the control can run up to four (4) on/ off boilers or three (3) mod boiler(s).
DIFFERENTIAL SETPOINT MODE –
Programming for this mode can be found on pages 25 through 28. This mode
is used when running a differential setpoint. In differential mode, the control will also send a modulating signal
output based on how far the control is from the differential. This can be used to run a pump in modulating
applications for constant flow.
DUAL SETPOINT MODE –
Programming for this mode can be found on pages 29 through 31. This mode is used
when one or two independent setpoints are needed. Each setpoint is set up individually and each has its own
thermistor input and relay outputs: Each setpoint has its own normally open and normally closed contacts
(which can be used for heating and/or cooling).
PUMP SEQUENCER MODE –
Programming for this mode can be found on pages 32 through 34. This mode is used
to provide pump control for two pumps in a duty, standby situation. This control allows the system to sequence
and cycle pumps, override pumps and turn the pumps off when the outdoor temperature goes above a
certain value (WWSD)
In the event you select the wrong control mode, please cycle power to the
controller and it will display the control mode option screen.
SensorLinx
TM
Mobile App
The Sensorlinx
TM
mobile app is available for Apple iOS (APP Store) and
Android® devices (Google Play). The mobile app allows for remote
monitoring and control for HBX Controls devices.
Now available on the Apple App Store and Google Play