Constellation™
November 2003
3-4 Installation
and
Commissioning
Circuit Breakers
The values in
are for the Constellation
terminal radio only.
Grounding Recommendations
Grounding in accordance with the R56 installation standard is necessary for
proper operation of the equipment as well as protection of the personnel and
equipment.
•
Connect the ground between the radio rack and halo, or ground window
of the site.
•
Do not connect the ground through any other radio or rack.
•
Do not daisy chain the grounds. A surge through a daisy chain ground
will go through all the radios.
•
The return bus bar should be grounded using 6-AWG wire as a
minimum.
Some operators require the same gauge wire for the return buss bar and the
battery cables. This may help avoid DC power surges when the on-site
generator switches between on or off.
Table 3-3: Recommended circuit breaker sizes for
Constellation radio terminal only
6, 7/8 GHz
10/11 GHz
Configuration
24 V
48 V
24 V
48 V
Fully protected
25 A
15 A
30 A
15 A
Summary of Contents for Constellation
Page 1: ...Point to Point Digital Radio Constellation Installation Maintenance...
Page 2: ......
Page 4: ...Constellation November 2003...
Page 18: ...Constellation November 2003 xii List of Figures...
Page 24: ...Constellation November 2003 xviii Preface...
Page 26: ...Constellation November 2003 xx Preface...
Page 96: ...Constellation November 2003 4 12 Loopback Testing...
Page 110: ...Constellation November 2003 5 14 Configuring the Constellation Radio...
Page 134: ...Constellation November 2003 7 14 SNMP Based Network Management...
Page 210: ...Constellation November 2003 11 36 Field Replaceable Units...
Page 238: ...Constellation November 2003 A 16 Wiring Specifications...
Page 260: ...Constellation November 2003 C 10 Hardware Compatibility Tables...
Page 276: ...Constellation November 2003 Glossary 6...
Page 291: ......