background image

29

7.0  Maintenance

WARNING - This equipment is a pressure-containing 

device. Depressurize before servicing.

Note

: The  Dryer  Controller  is  equipped  with  Service 

Reminder functions for filters, desiccant and valves.

7.1  Desiccant Replacement

NOTE:

 The use of the correct replacement desiccant 

is  necessary  for  proper  dryer  operation.  Never  use 

hygroscopic  salts  of  the  type  commonly  used  in 

“deliquescent ” type dryers.

1.  Frequency Of Desiccant Replacement

 

Desiccant should be replaced whenever the required 

dew point cannot be maintained while the dryer is 

being operated within its design conditions and there 

are no mechanical malfunctions.

 

NOTE:

 Desiccant life is determined by the quality of 

the inlet air. Proper filtering of the inlet air will extend 

the life of the desiccant. Typically desiccant life is 2 

years.

2.  Procedure for Desiccant Charge Replacement

a.  Depressurize and de-energize the dryer.
b.  Remove the fill and drain plugs or flanges (where 

applicable) from the desiccant tower and drain the 

spent desiccant. Place a container at the base of 

the vessel to collect the desiccant. If necessary 

tap the sides of the vessels with a rubber mallet 

to loosen desiccant. 

 

NOTE:

  Use  extreme  care  when  inserting  rods  or 

other tools through the desiccant fill or drain ports 

to loosen packed desiccant. Internal flow diffusers 

at the ends of the desiccant beds can be damaged 

or punctured by sharp instruments. These diffusers 

are necessary to distribute the airflow and keep the 

desiccant beads within the tower. Desiccant beads in 

exhaust mufflers, afterfilters, or the piping connected 

to the desiccant towers may indicate a perforation of 

a diffuser.
c.  Replace the drain plug using Teflon tape or another 

pipe thread sealant suitable for compressed air 

service.  Reinstall drain port flange cover (where 

applicable) in each desiccant tower.

d.  Refer to Table 1 (on page 5) for desiccant 

quan-

tity per tower.

  When using Table 1 you will find the desiccant 

quantities listed in layers.  Each layer will vary in 

depth due to the type, quantity and purpose of the 

desiccant.  Layer 1 must be installed first at the 

bottom of the vessel followed by layer number 2 

etc., until the complete charge of desiccant has 

been installed.

e.  Utilizing  an  appropriate  sized  funnel,  fill  each 

desiccant tower as follows:
1)  Install the required quantity of tabular support 

(model  4300  only)  or  activated  alumina  in 

layer 1 of each tower.

2)  Level layer 1 and each subsequent layer of 

desiccant as added to each tower.

3)  Finish filling each tower with desiccant until 

all desiccant has been installed.  LIGHT tap-

ping on the tower sides with a soft-face mallet 

should  yield  additional  free  space  to  allow 

installation of all desiccant required.  

DO NOT 

TAMP OR RAM DESICCANT

.

f.  Clean the fill port closure.  Replace the fill plug 

using Teflon tape or another pipe thread sealant 

suitable for compressed air service.  Reinstall fill 

port flange cover (where applicable) in desiccant 

tower.

3.  Insuring Desiccant Dryness

 

Replacement  desiccant  is  shipped  in  airtight 

containers. Keep the covers on these containers tightly 

closed  until  use  to  avoid  moisture  contamination. 

If  desiccant  is  exposed  to  air  it  can  be  heated  in 

an  oven  at  400°F  (204°C)  for  four  hours  before 

use. Alternatively,  if  the  dryer  is  not  refilled  with 

dry  desiccant,  it  may  be  necessary  to  operate 

the unit with an inlet flow rate of less than 50% of 

maximum rated inlet capacity until the desiccant has 

regenerated fully.

7.2  Purge Mufflers

Purge mufflers should be checked regularly, changed 

annually. Muffler disseminator elements become clogged 

with desiccant dust over time, creating back pressure 

and restricted purge flow.

7.3  Valves

1.  Process  and  pilot  valves  should  be  checked  fre-

quently for leaks and proper operation.

2.  Purge pressure adjustment valve should be checked 

frequently for proper adjustment.

7.4  Pilot Air Filter Element Replacement

1.  Frequency of replacement

 

 

The pilot air filter contains a filter element that should 

be changed yearly. Replacement may be required 

sooner if pressure drop across cartridge prevents 

valves from actuating properly.

Warning  –

  The  pilot  air  filter  housing  is  a  pressure-

containing  device,  depressurize  before  servicing. 

Slowly  open  manual  drain  valve  on  bottom  of  filter 

bowl by turning clockwise to verify that the housing is 

depressurized before removing bowl.

Summary of Contents for HBP Series

Page 1: ...36 Electrical Schematic 460VAC 3 phase 38 Electrical Schematic 575VAC 3 phase 39 Electrical Schematic 380VAC 3 phase 40 Electrical Schematic 415VAC 3 phase 41 Electrical Data Fusing Wire Sizing 42 WAR...

Page 2: ...R WARNING and CAUTION are used to indicate hazard seriousness levels as follows DANGER Immediate hazard which will result in severe injury or death WARNING Hazard or unsafe practice which could result...

Page 3: ...ryer in order to protect the desiccant bed from liquid and solid contamination Use an Air Line Filter in systems sup plied by a non lubricated oil free air compressor In systems supplied by a lubricat...

Page 4: ...lectrical enclosure for a remote alarm The contact ratings are shown on the electrical drawing Compressor Aftercooler Separator Receiver Prefilters Afterfilters Receiver Desiccant Dryer Figure 1 Typic...

Page 5: ...ty and purpose of the desic cant Layer 1 must be installed rst at the bottom of the vessel followed by layer number 2 etc until the complete charge of desiccant has been installed 4 Utilizing an appro...

Page 6: ...E MAX F G C D B A MAX H K N MAX P L S GAS INLET M FACE OF CUSTOMER WET GAS INLET CONNECTION FACE OF CUSTOMER DRY GAS OUTLET CONNECTION R SLOT TYP 4 PLACES TOP VIEW SIDE VIEW RIGHT CHAMBER REMOVED FOR...

Page 7: ...NPT 3 FLANGE 3 FLANGE 3 FLANGE 3 FLANGE 3 FLANGE 4 FLANGE 4 FLANGE 4 FLANGE 4 FLANGE 6 FLANGE 6 FLANGE T 2 NPT 2 NPT 3 FLANGE 3 FLANGE 3 FLANGE 3 FLANGE 3 FLANGE 4 FLANGE 4 FLANGE 4 FLANGE 6 FLANGE 6...

Page 8: ...ge mounted on the gauge panel of the dryer indicates purge air pressure 5 4 Energy Management System The optional Energy Management System EMS automatically adjusts dryer operation to compensate for c...

Page 9: ...DRAIN PORT TOWER INSULATION OPTIONAL CONTROL ENCLOSURE HIGH TENSION ENCLOSURE RIGHT TOWER PRESSURE GAUGE PURGE PRESSURE GAUGE REPRESS VALVE HEATER TEMP THERMOCOUPLE CENTER END IN PIPE OPPOSITE SIDE H...

Page 10: ...ER DEPRESS VALVE ASME RELIEF VALVE REPRESS VALVE TOP VIEW FRONT VIEW PURGE HEATER WITH INSULATION PURGE SUCTION FILTER SILENCER PURGE BLOWER AND MOTOR REAR VIEW LEFT TOWER INLET VALVE ASME CODE TAG LE...

Page 11: ...DEPRESS VALVE DESICCANT DRAIN PORT TOWER INSULATION OPTIONAL HIGH TENSION ENCLOSURE CONTROL ENCLOSURE RIGHT TOWER PRESSURE GAUGE PURGE PRESSURE GAUGE REPRESS VALVE PURGE BLOWER AND MOTOR PURGE BLOWER...

Page 12: ...slowly depressurized Air exits through exhaust muf er M2 After the right tower has depressurized the Right Purge Valve V4 is opened and the Blower M and Heater H1 are energized The heated air ows thro...

Page 13: ...LEFT TOWER SET 45 PSIG M RTD 3 SET 650 F 1TC SET 370 F V5 2PS SET 176 F 4PS SET 5 PSIG REGEN SET 45 PSIG SET AT 100 PSIG RIGHT TOWER V8 V12 V13 SOL E V7 V11 RV1 SET 165 PSIG DEWPOINTER OPTION DPA SOLE...

Page 14: ...d because the repressurization step will occur before the bed temperature can fall to 150 F Note In Energy Management or Dew Point Control as the drying time extends beyond 4 hours additional cooling...

Page 15: ...is installed in the OFF position if Switching Failure is disabled 6 JP6 Not Used NOTE Jumpers JP7 and JP8 are used by the factory during nal inspection to download language text and to enable factory...

Page 16: ...for the Heated Desiccant Dryer Control a Program Mode b Setup Mode c Alarm Service Mode d Display Mode e Test Mode 2 Each Mode is described below 6 5 4 Program Mode 1 Press and hold and for 3 seconds...

Page 17: ...Point Demand Control Displayed only when JP3 on DPNT CNTL SETPT XX C XXX F 1 Press to increment the setting to the desired value a Standard set point is 30 C 22 F b The allowable range of values is fr...

Page 18: ...m Vapor Pressure Set Point screen 9 4 When nished press to acknowledge the se lection and scroll to the switchover delay set point screen a Factory set point is 60 MIN b The allowable range of values...

Page 19: ...ing the drying cycle b Left or Right tower regenerating high pressure i Regenerating tower pressure switch is closed while purge valve is open after an initial time delay c Left or Right tower regener...

Page 20: ...UNDER RANGE ALARM RIGHT TWR DEW POINT OVER RANGE ALARM LEFT TOWER TEMP UNDER RANGE ALARM LEFT TOWER TEMP OVER RANGE ALARM RIGHT TWR TEMP OVER RANGE ALARM RIGHT TWR TEMP UNDER RANGE ALARM RIGHT TWR DR...

Page 21: ...rogram Mode b Humidity Sensor i Under range RH 15 ii Over range RH 115 c RTD i Over range Temperature above 448 F 231 C ii Under range Temperature below 20 F 28 C d On alarm condition i Local alarm is...

Page 22: ...upplied to the controller whether the controller is switched on or off When a service time interval expires see also 14 d below the controller operates as follows a The service LED blinks and the appr...

Page 23: ...e reminder lters HOURS TO SERVICE FILTERS XXXX Service reminder desiccant HOURS TO SERVICE DESICCANT XXXX Service reminder valves HOURS TO SERVICE VALVES XXXX Outlet Dew Point Displayed only if JP3 is...

Page 24: ...ying Drying Drying Drying 1PS Closed Closed Closed Closed Closed Closed Closed then Open Open Open Open then Closed 2PS Closed Closed then Open Open Open Open then Closed Closed Closed Closed Closed C...

Page 25: ...pressurized Exception If switching failure is disabled then pressure condition is ignored Screen 6 Step 6 TEST6 RT DRYING RT XX C XXX F Screen 7 Step 7 TEST7 DEPR LT LT XX C XXX F Note Sequence step...

Page 26: ...d 600 Inlet switching valves are normally open pneumatically piston actuated Y angle poppet valves Ayellow indicator can be seen through a clear window at the top of the ac tuator housing when the val...

Page 27: ...ization valve closes 6 9 1 2 On restoration of power 1 If power is lost when the off line tower is in either the HEAT or COOL step the off line tower will be either partially or fully repressurized On...

Page 28: ...ASCII representation of the energy savings x Reserved for future use always 1 for now ETX end of text character OxO3 CR carriage return LF line feed JUMPERS The programming jumpers are as follows 0 o...

Page 29: ...Layer 1 must be installed rst at the bottom of the vessel followed by layer number 2 etc until the complete charge of desiccant has been installed e Utilizing an appropriate sized funnel ll each desi...

Page 30: ...Replacement may be required sooner if pressure drop across cartridge prevents the Dew Point Analyzer from operating properly Warning The Dew Point Analyzer lter housing is a pressure containing device...

Page 31: ...k Valve leak ing 1 Check compressor supplying dryer 2 Check equipment downstream of dryer 3 Check pressure switch operation using tower pressure gauge for comparison Replace switch if defective 4a Che...

Page 32: ...3 Regenerating tower Depressurization Valve failed to close 4 Repressurization valve V11 failed to open 5 Repressurization ori ces are blocked 1 Check pressure switch operation using tower pressure ga...

Page 33: ...ins Repair or replace as necessary Useful life of desiccant has been exceeded Heater Over Temperature Alarm 1 Insuf cient purge gas ow 2 Temperature sensor failure 1 Check for purge blockage temperatu...

Page 34: ...SOL C 2 1 3 LEFT TOWER SET 45 PSIG M RTD 3 SET 650 F 1TC SET 370 F V5 2PS SET 176 F 4PS SET 5 PSIG 18 REGEN 9 SET 45 PSIG SET AT 100 PSIG RIGHT TOWER 12 11 8 7 V8 26 V12 V13 SOL E V7 V11 SET 165 PSIG...

Page 35: ...43 ENERGY MANAGEMENT SENSOR RTD4 HS1 DEWPOINTER OPTION 44 DEWPOINT ANALYZER 44A DEWPOINT ANALYZER FILTER INSULATION OPTION 54 CHAMBER INSULATION LEFT CHAMBER DRYING RIGHT CHAMBER REGEN CLOSED NO 3 WA...

Page 36: ...TD 3 SET 650 F 1TC SET 370 F V5 V6 2PS REGEN SET 176 F 4PS SET 5 PSIG 18 9 RIGHT TOWER SET 45 PSIG SET AT 100 PSIG 12 11 8 7 26 V12 V13 SOL E V11 V7 V8 SET 165 PSIG DEWPOINTER OPTION DPA 15 3 22 14 13...

Page 37: ...AGEMENT SENSOR RTD4 HS1 DEWPOINTER OPTION 44 DEWPOINT ANALYZER 44A DEWPOINT ANALYZER FILTER INSULATION OPTION 54 CHAMBER INSULATION FAILS IN POSITION LEFT CHAMBER DRYING RIGHT CHAMBER REGEN CLOSED NO...

Page 38: ...ENERGY MGMT OPTION RTD4 1HTR 102 101 102 102 102 1CR 102 101 101 101 109 111 101 107 SOLENOID C 21 LEFT CHAMBER PURGE EXHAUST HEAT ENABLE C NO 101 102 20 21 80 81 70 72 21 10 11 84 85 86 87 88 89 32 3...

Page 39: ...2HC2 2HC3 507 508 509 4 20MA OUT ENERGY MGMT OPTION RTD4 2HTR 102 101 102 102 102 1CR 102 101 101 101 109 111 101 107 SOLENOID C 21 LEFT CHAMBER DEPRESS LEFT CHAMBER PURGE EXHAUST HEAT ENABLE C NO 101...

Page 40: ...ON RTD4 1HTR 102 101 102 102 102 1CR 102 101 101 101 109 111 101 107 SOLENOID C 21 LEFT CHAMBER DEPRESS LEFT CHAMBER PURGE EXHAUST HEAT ENABLE C NO 101 102 20 21 80 81 70 72 21 10 11 84 85 86 87 88 89...

Page 41: ...101 102 102 102 1CR 102 101 101 101 109 111 101 107 SOLENOID C 21 LEFT CHAMBER DEPRESS LEFT CHAMBER PURGE EXHAUST HEAT ENABLE C NO 101 102 20 21 80 81 70 72 21 10 11 84 85 86 87 88 89 32 33 34 35 50...

Page 42: ...AWG 4300 HEATER 2 35 KW 2 35 1 2 40 AMPS 2 8 AWG MOTOR 7 5 HP 9 15 AMPS 12 AWG Models 3200 3600 and 4300 use a two stage heater circuit with two contactors six fuses and six wires Electrical Service...

Page 43: ...43...

Page 44: ...arranty and any resulting charge or subsequent claim will not be paid THE FOREGOING WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES WRITTEN ORAL OR STATUTORY AND IS EXPRESSED IN LIEU OF THE...

Reviews: