17
b. SEVERE Service Intervals are:
i. 2000 hours for filters
ii. 4000 hours for desiccant
iii. 4000 hours for valves
2. When finished, press to save the selection and
move to next screen.
Screen 3: Reset the Timer for Filter Service
FILTER SERVICE
RESET? NO
1. Press to toggle between NO and YES.
2. When finished, press
to acknowledge the
selection and move to next screen.
Screen 4: Reset the Timer for Desiccant Service
DESICCANT SERVICE
RESET? NO
1. Press to toggle between NO and YES.
2. When finished, press
to acknowledge the
selection and move to next screen.
Screen 5: Reset the Timer for Valve Service
VALVE SERVICE
RESET? NO
1. Press to toggle between NO and YES.
2. When finished, press to acknowledge the selec-
tion and move to next screen.
Screen 6: Set Alarm Point for the Dew Point
Sensor
(Displayed only when JP3 “on”)
DEWPOINT ALARM
±XX°C
±XXX°F
XX MIN SW DELAY
1. Press
to increment the setting to the desired
value.
a. Standard set point is
-20°C
-4°F
.
b. The allowable range of values is from
-80°C
-112°F
to
+10°C
+50°F
in 5°C/9°F
increments.
2. When finished, press
to acknowledge the se-
lection and scroll to the switchover delay set point
screen.
a. Standard set point is
60 MIN
.
b. The allowable range of values are
30 to 120 MIN
in 10 minute increments.
3. When finished, press to acknowledge the selec-
tion and move to next screen. Exit Program Mode
when there are no more active screens to display.
Screen 7: Set Point for Dew Point Demand Control
(Displayed only when JP3 “on”)
DPNT CNTL SETPT
±XX°C
±XXX°F
1. Press
to increment the setting to the desired
value.
a. Standard set point is
-30°C
-22°F
.
b. The allowable range of values is from
-80°C
-112°F
to
+10°C
+50°F
in 5°C/9°F
increments.
Note:
Must be set “drier” than Dew Point Sensor
Alarm Set Point (screen 6).
2. When finished, press
to acknowledge the
selection and exit the Program Mode.
Screen 8: Set the Heat Termination Set Point
HEAT TERM SET-PT
XX°C
XXX°F
1. Press
to increment the setting to the desired
temperature value.
a. Refer to P&ID diagrams in the back of this manual
for Heat Termination set points (see set point
values for RTD1 and RTD2).
b. The allowable range of values are:
60° - 160°C
140° - 320°F
in 10°C increments.
2. When finished, press to acknowledge the selec-
tion and move to next screen. Exit Program Mode
when there are no more active screens to display.
Screen 9: Set Points for Energy Management
(Displayed only when JP8 “on”)
ENRGY MGMT SETPT
XX%RH
XX MBAR .XXX PSI
1. Press
to increment the setting to the desired
maximum RH value.
a. Factory set point is
60%RH
. The factory setting
should not require adjustment.
b. The allowable range of values are
20 to 80%RH
in 5% increments.
2. When finished, press to acknowledge the selec-
tion and scroll to the pressure set point screen.
3. Press
to increment the setting to the desired
maximum vapor pressure value.
a. Standard set point for a -40°F dew point dryer is
16 MBAR (0.232 PSI)
.
Note:
Standard set point for a -100°F dew point
dryer is
4 MBAR (0.058 PSI)
.
b. The allowable range of values is
3 to 34 MBAR (0.044 to 0.493 PSI)
in 1 MBAR
increments.