RC2-D Technical Manual
Figure 3-4 25%
、
50%
、
75%
、
100% Loading schematic diagram
◎
Note:
ON: the solenoid valve is activated; OFF: the solenoid valve is not activated
3.2.2
Continuous loading of compressor
Since it will take a long time for compressor to reach the required working conditions, the compressor
shall be started at 25% or 33% loading and kept for about 30 seconds (the startup time length
recommended by Hanbell).
Then the compressor is gradually loaded to 50% (66%) in time "t" and then
loaded to 75% in another"t" time. The time "t" is determined according to different working conditions
and application conditions.
Figure 3-5 Continuous loading time chart of compressor