RC2-D Technical Manual
pressure gas return port of the compression chamber, and then install an economizer check valve to
reduce the vibration caused by the medium pressure gas return. For the connection between muffler and
check valve, please refer to the application system in Chapter 7
.
5.2.15 External Oil filter
For parallel connection system, an external oil filter must be installed on the return line to ensure the
cleanliness of the oil return. If the pipeline is too dirty, secondary filtration must be added to ensure the
compressor is in safe operation. The oil filter is of washable type, with the precision of 300 meshes. See
the following figure for the dimensions. The thread / welding ports of the inlet and outlet are connected
with 3 / 8 ", 5 / 8" and 1 "copper pipes.
Figure-External Oil filter
5.2.16 Oil flow switch
The oil flow switch should be installed in the system with external oil separator to prevent oil loss of the
compressor. The specifications and installation are as follows:
Installation diagram of oil flow switch
Type
Connection
Pipe size
Applicable model
Thread weld
(
d
)
138
型
Thread/weld
3/8"
Φ10
RC2-100~310D-P
138
型
Thread/weld
5/8"
Φ16
RC2-340~620D-P
138
Weld
1"
Φ25.5
RC2-710~930D-P
Size
Connection
Model
3/8"
Thread/Weld RC2-100~180D-P
5/8"
Thread/Weld RC2-200~620D-P
1”
Weld
RC2-710~930D-P
Summary of Contents for RC2-D
Page 27: ...RC2 D Technical Manual 2 RC2 200 470 D S P terminal box 3 RC2 510 930 D S P terminal box ...
Page 45: ...RC2 D Technical Manual 47 RC2 180D S Drawing ...
Page 46: ...RC2 D Technical Manual 48 RC2 200 620D S Horizontal suction port Drawing ...
Page 48: ...RC2 D Technical Manual 50 RC2 620 930D S Vertical suction port Drawing ...
Page 49: ...RC2 D Technical Manual 51 10 2 RC2 100 930D P Drawing RC2 100 140D P Drawing ...
Page 50: ...RC2 D Technical Manual 52 RC2 180D P Drawing ...
Page 51: ...RC2 D Technical Manual 53 RC2 200 620D P Drawing ...