b.
The grounding voltage of terminal box shall not be greater than 50V; in humid area, it should be 25V.
c.
The grounding resistance shall not be greater than 50
Ω
.
d.
Air cut board (ACB) is usually connected with leakage protector. Please refer to relevant operation
settings.
e.
Once the leakage protection is started, please check if the insulation is normal and if the circuit and
setting are correct. Please turn on the power after confirmation. If you have any questions, please
contact the equipment supplier.
Specification for terminal plate nut
Model
Specification
Torque(N.m)
RC2 -100~180D-S(P)
M8
20
RC2 -200~930D-S(P)
M12
35
Note:
when the surface temperature of compressor is lower than the air dew point
temperature, it is recommended to wrap the exposed part of the wiring with electrical
insulation tape to improve reliability