• Switch the heating mode to automatic
AUTO
Diagrams: VX102 / VX112
page 6 / 6
Line No. Value
• Configuration
menu
Activate the heating circuits' frost
protection mode
Frost protection plant (6120)
On
Optimisation of DHW:
Line No. Value
• DHW storage tank
menu
Adjust the boost
Starting value of boost temperature (5020)
16 °C
Maintenance optimisation:
It is possible to generate a maintenance message without harming the boiler. This maintenance
message may appear when the 3 following meters have elapsed:
• Time since last maintenance (or commissioning): set parameter 7044 to 12 months
• Operating hours of the burner (parameter 7040)
• Number of start-ups (parameter 7042)
The last 2 parameters depend on the boiler room's hydraulic installation. It is recommended to
use at least parameter 7044 for yearly maintenance.
G. SETTING AMBIENT SENSORS
Connect each sensor to a heating circuit:
Line No. Value
• User interface
menu of
each ambient sensor
Configure the ambient sensor with a heating circuit
Use (40)
Ambient appliance
1 or 2 or 3
Each ambient sensor allows its heating circuit to be configured. Ambient sensors 1, 2 and 3 respectively
set parameters 712 (heating circuit 1), 1012 (heating circuit 2) and 1312 (heating circuit 3).