VARMAX -
Installation, Use and Maintenance
On boiler No. 2: slave
• Input/output test
menu
Check the outputs
Alarm relay
Relay test (7700)
Relay output QX1
Insulating valve Q1.2
Relay test (7700)
Relay output QX3
Reset outputs
Relay test (7700)
No test
Line No.
Value
F. OPTIMISATION OF SETTINGS
Optimisation of the cascade:
The cascade may be optimised as required with the parameters of the
Cascade
menu. Refer to the
LMS boiler command table instructions for more details.
Diagram VX211
page 6 / 6
Maintenance optimisation:
It is possible to generate a maintenance message without harming the boiler. This maintenance
message may appear when the 3 following meters have elapsed:
• Time since last maintenance (or commissioning): set parameter 7044 to 12 months
• Operating hours of the burner (parameter 7040)
• Number of start-ups (parameter 7042)
The last 2 parameters depend on the boiler room's hydraulic installation. It is recommended to
use at least parameter 7044 for yearly maintenance.