80 / 156
00BNO9168-I (U0606551)
VARMAX -
Installation, Use and Maintenance
Optimisation of DHW:
Line No. Value
• Domestic hot water
menu
Set the reduced setting
Reduced setting (1612)
- - -
Set the DHW release mode
DHW release (1620)
Time programme 4/
DHW
• Time programme 4 / ECS
menu
Preselection
Preselection (560)
- - -
Adjust the time programme
On / Off phases (561...566)
- - -
• DHW storage tank
menu
Adjust the boost
Starting value of boost temperature (5020)
- - -
• Domestic hot water
menu
Configure an anti-legionella function
Anti-legionella function (1640)
- - -
Periodic anti-legionella function
(1641)
- - -
Day week anti-legionella function (1642)
- - -
Anti-legionella temperature setting (1645)
- - -
Duration of anti-legionella function (1646)
- - -
Maintenance optimisation:
It is possible to generate a maintenance message without harming the boiler. This maintenance
message may appear when the 3 following meters have elapsed:
• Time since last maintenance (or commissioning): set parameter 7044 to 12 months
• Operating hours of the burner (parameter 7040)
• Number of start-ups (parameter 7042)
The last 2 parameters depend on the boiler room's hydraulic installation. It is recommended to
use at least parameter 7044 for yearly maintenance.
Diagram VX110
page 5 / 5