14.09.2020
145 / 156
VARMAX -
Installation, Use and Maintenance
Line
No.
Programme
Access
Default value
Customer setting
2470
Delay heat req special op
C
0 s
2503
Parameter
S
--- s
2630
Auto deaeration procedure
S
Off
2655
ON time deaeration
S
10 s
2656
OFF time deaeration
S
5 s
2657
Number of repetitions
S
3
2662
Deaeration time heat circuit
S
10 min
2663
Deaeration time DHW
S
5 min
Cascade
3510
Lead strategy
S
Early on, late off
3511
Output band min
S
30 %
3512
Output band max
S
90 %
3530
Release integral source seq
S
50 °Cmin
3531
Reset integral source seq
S
20 °Cmin
3532
Restart lock
S
300 s
3533
Switch on delay
S
5 min
3534
Forced time basic stage
S
60 s
3535
Switch-on delay DHW
S
2 min
3540
Auto source seq ch'over
S
500 h
3541
Auto source seq exclusion
S
none
3544
Leading source
S
source 1
3560
Return setpoint min
S
8 °C
3562
Return influence consumers
S
On
DHW storage tank
5020
Flow setpoint boost
S
10 °C
5021
Transfer boost
S
8 °C
5022
Type of charging
S
Full charging
5030 Charging time limitation
S
--- min
5040 Discharging protection
S
Automatically
5050
Charging temp max
S
80 °C
5055
Recooling temp
S
80 °C
5056
Recooling heat gen/HCs
S
Off
5057
Recooling collector
S
Off
5060
El imm heater optg mode
S
Substitute
5061
El immersion heater release
S
DHW release
5062
El immersion heater control
S
DHW sensor
5085
Excess heat draw
S
On
5090
With buffer
S
No
5092
With prim contr/system pump
S
No
5093
With solar integration
S
Yes
5101
Pump speed min
S
100 %
5102
Pump speed max
S
100 %
5108
Starting speed charg pump
S
100 %
General functions
5570
Temp diff on dT contr 1
S
20 °C
5571
Temp diff off dT contr 1
S
10 °C
5572
On temp min dT contr 1
S
0 °C
5573
Sensor 1 controller 1
S
None
5574
Sensor 2 controller 1
S
None