Line No. Value
For a demand via LPB (LPB network menu)
• LPB network
menu
Check that the boiler has been defined
as the master generator
Appliance address (6600)
1
Segment address (6601)
0
Bus supply function (6604)
Automatic
Clock function (6640)
Slave with
adjustment
E. ELECTRICAL AND HYDRAULIC VALIDATION
For a demand via input 0...10V
• Input/output test
menu
Voltage in H1
Voltage signal H1 (7840)
To validate with
the voltage sent
by the boiler room
machine
For a demand via LPB
If the boiler room regulator is configured as the master clock, the boiler
command table must recover the date and time.
In both cases
F. OPTIMISATION OF SETTINGS
Diagram VX111
page 3 / 3
Maintenance optimisation:
It is possible to generate a maintenance message without harming the boiler. This maintenance
message may appear when the 3 following meters have elapsed:
• Time since last maintenance (or commissioning): set parameter 7044 to 12 months
• Operating hours of the burner (parameter 7040)
• Number of start-ups (parameter 7042)
The last 2 parameters depend on the boiler room's hydraulic installation. It is recommended to
use at least parameter 7044 for yearly maintenance.
Warning
the boiler considers a heat demand for a voltage H1> 0.2 V and a resulting setpoint> 6 ° C *.
The boiler no longer considers a heat demand for a voltage H1 <0.2V or a resulting setpoint <4 ° C *.
In this second case, the boiler isolation valve will close. If the installation does not include a hydraulic
decoupling bottle, all the network pumps must be stopped at the risk of causing them to cavitate.
* : according to scale given in parameter "5956"