MAN1544-5
19
4.1.2
Fault Test
Once the test is commenced the Buzzer will rapidly turn on and off and the common Fault and Zone Fault
LED’s will flash. Press
,
the Buzzer will be silenced and the common Fault and Zone Fault LE
D’s
will continue to flash. Press
to return the panel to normal. The LCD will indicate the Fault Test
has been implemented on the selected Zone.
FLT TST
ZONE 1
Figure 11: Fault Test Zone 1 Screen
4.1.3
Walk Test
Note:
The Brigade, Agent Release and any other system specific signalling should be ISOLATED prior to
initiating this test.
A Walk Test, sets the Zone to Non latching and allows the technician to test detectors and MCP’s on that
Zone. When a detector or MCP is
put into alarm the “Alarm Outputs” will operate, the corresponding “Zone
Alarm” LED will flash and the buzzer will sound.
The Zone will stay in Alarm until the MCP, or detector under test is reset or, the test is aborted by pressing
Cancel or, the test times out. The time out period can be set by pressing
once the Zone has been
selected and using the
Move Up and / or
Move Down keys to select the required time for
the test. The default time is 5 minutes but can be adjusted from 1 to 20 minutes by again using the
Move Up and / or
Move Down keys to select the required time and then pressing
.
WLK TST
ZONE 1
TEST END
5 mins
CANCEL
TO END
Press
Enter Time
In the TEST END screen the operator has ten (10) seconds to enter the time before the test will commence
OR, the test can be started by pressing
.
Only one zone at a time can be in test mode, all other zones will operate as normal.
The LCD will display which Zone is the in Walk Test mode.