MAN1544-5
34
5.3.10
Display
To set the message, FACP or company name press
and use the
Move Right and
Move Left
keys to move through the word to select a letter and the
Move Up and the
Move Down
keys to move through the alphabet. A maximum of 16 characters are available for this message.
AMPAC
< INFO >
Press
to update each Program and
to back out of the Menu.
5.3.11
Zone Labels
To name the Zones press
then the
Move Right and / or the
Move Left keys to select a
Zone. Press
and use the
Move left and / or
Move Right keys to move the cursor through
the structure of the word and the
Move Up and
Move Down keys to move through the
alphabet.
Z LABELS
ZONE 1
Z1 : LOBBY
Press
to update each Program and
to back out of the Menu.
5.3.12
End Of Line (EOL)
Press
and use the
Move Up and
Move Down keys to select the EOL option. The
options are CAP 10
f, RES 3K3 (AS factory default value), 4K7, 6K8 and 10K.
EOL
CAP 10uF
EOL
RES 3K3
EOL
RES 4K7
Press
Enter
to update each Program and
Cancel
to back out of the Menu.
5.3.13
Zone S/C
Press
and use the
Move Up or
Move Down key to set the panel to initiate either an
Alarm or Fault when a Zone short circuited condition exists.
ZONE S/C
ALARM
ZONE S/C
FAULT
Press
Enter
to update each Program and
Cancel