MAN1544-5
20
4.1.4
Lamp Test
Press the
Move Right and / or
Move Left key to move to the Lamp Test menu, press
and
each LED on the panel will be sequentially turned on for one second and then off again. The Buzzer will
sound at the start and completion of the test.
LAMP TST
LAMP >>>>>>
>>>>>>>>TST
TEST...............
COMPLETE
Press
Indicates the Test Progress
Test Successful
Note:
The operator has to visually confirm each LED illuminates.
4.1.5
Battery Test
Press the
Move Right and / or
Move Left key to move to the Battery Test menu, Press
and
the Battery Test will commence, that is the Charger will be disconnected from the battery and a dummy
load placed across the battery for 60 seconds. The battery voltage should be above that specified (23.5
volts) at the end of the testing period, if not a FAILED message is displayed.
BATT TST
26.1
BATT TST
PASS
BATT TST
FAIL
Battery Test Underway
Test Successful
Battery Failure
4.1.6
Sounder Tests of each Sounder
Press the
Move Right and / or
Move Left key to move to the Sounder Test menu, press
,
then select the Sounder by using the
Move Up and / or
Move Down keys until the desired
Sounder number is displayed, press
to start the test and
to turn it off.
SNDR TST
SNDR TST
6
Press
Sounder 6 Selected
to Start
to Stop