SETUP ZONE OPTIONS
Zone options are parameters that define the way that a zone functions. There are global zone options that affect all zones and
there are individual zone options that affect how each individual zone functions.
To configure zone options, from the Installer Setup menu, press the 8 (ZOPT) key.
SWINGER SHUTDOWN NUMBER
Swinger Shutdown is a false alarm prevention feature that counts the number of alarms caused by a specific zone. After a certain
number of alarms caused by the same zone within the same arming period, the controller will then shutdown that zone for the
remainder of that arming period.
The "Swinger Shutdown Number" is the number of times that a zone may cause an alarm during the same arming period before it
is shutdown.
SWINGER SHUTDOWN NUM: 1
1-2
↓
When enabled, if the Swinger Shutdown zone is violated (causes an alarm) 1 or 2 times (according to the “Swinger Shutdown
Number”) within the same arming period, the controller will then shutdown and ignore that zone for the remainder of that arming
period.
The default setting is 1.
CROSS ZONE WINDOW
Cross Zoning is a feature that enforces redundant detection of devices such that two or more zones must trip within a defined
period to cause an alarm. This feature is typically used when multiple devices are used to cover the same general area.
The "Cross Zone Number" is the number of seconds in which a second zone must trip after a zone configured as “Cross Zoning”
has been tripped in order to cause an alarm.
CROSS ZONE NUMBER: 60
15-240 SECONDS
The default setting is 60 seconds.
ZONE 1 OPTIONS – ZONE 48 OPTIONS
Each zone has individual zone options that may be configured for Cross Zoning, Swinger Shutdown, and Dial Out Delay.
ZONE 1 OPTIONS: 4
0-7
THROUGH
ZONE 48 OPTIONS: 4
0-7
↑
Enter a single value to configure the individual zone options for each zone according to the table below:
Zone Options Table
Zone Options Value
0
1
2
3
4 5 6 7
Cross Zoning
No Yes No Yes No Yes No Yes
Swinger Shutdown
No No Yes Yes No No Yes Yes
Dial Out Delay
No No No No Yes Yes Yes Yes
The default value for Zone 1 Options – Zone 48 Options is 4.
See
the highlighted area of Zone Options Table.