Installation Manual
H3C S5600 Series Ethernet Switches
Chapter 3 Installing the Switch
3-13
Screw 2
Screw 1
Cabinet
Connector
component
Screw 2
Screw 1
Cabinet
Connector
component
Figure 3-18
Fix RPS connector to the cabinet
Step 3: After installing connector component, directly insert the component into
DC-input socket on the cabinet, and then fix the screws 1 and 2 carried by the
connector itself to the appropriate holes on the cabinet socket using a small flathead
screwdriver, see Figure 3-18.
Step 4: Check that the RPS LED on the front panel of the switch is ON.
Caution:
z
Before powering on the switch, connect the ground wire.
z
The DC power cable should be less than 3 meters long.
z
The S5600-26C-PWR/S5600-50C-PWR must use the external PoE PSU
recommended by H3C as its DC input, but not the -48VDC power supply generally
available in the equipment room. Otherwise, the device may be damaged.
3.4.3 Connecting the Ground Wire
Caution:
Correctly connecting the switch ground wire is crucial to the lightning protection and
electromagnetic susceptibility (EMS) of a switch.
The power input end of the switch is connected with a noise filter, whose central ground
is directly connected to the chassis, forming the chassis ground (commonly known as