Specifications
epc1292Voltage
.50.1.5.1.2.1.6.x
Gauge32
RO
Actual Voltage on Power Channel
epc1292Frequency
.50.1.5.1.2.1.7.x
Gauge32
RO
Frequency of Power Channel
epc1292PowerFactor
.50.1.5.1.2.1.8.x
Integer32
RO
Power Factor of Channel between -1.0 and 1.00
epc1292Pangle
.50.1.5.1.2.1.9.x
Integer32
RO
Phase Angle between Voltage and L Line Current between -180.0 and
180.0
epc1292PowerApparent
.50.1.5.1.2.1.10.x
Integer32
RO
L Line Mean Apparent Power
epc1292PowerReactive
.50.1.5.1.2.1.11.x
Integer32
RO
L Line Mean Reactive Power
epc1292AbsEnergyReactive
.50.1.5.1.2.1.12.x
Gauge32
RO
Absolute Reactive Energy counter.
epc1292AbsEnergyActiveReset-
table
.50.1.5.1.2.1.13.x
Gauge32
RW
Resettable Absolute Active Energy counter. Writing '0' resets all reset-
table counter.
epc1292AbsEnergyReactiveReset-
table
.50.1.5.1.2.1.14.x
Gauge32
RO
Resettable Absolute Reactive Energy counter.
epc1292ResetTime
.50.1.5.1.2.1.15.x
Gauge32
RO
Time in seconds since last Energy Counter reset.
epc1292ForwEnergyActive
.50.1.5.1.2.1.16.x
Gauge32
RO
Forward Active Energy counter.
epc1292ForwEnergyReactive
.50.1.5.1.2.1.17.x
Gauge32
RO
Forward Reactive Energy counter.
epc1292ForwEnergyActiveReset-
table
.50.1.5.1.2.1.18.x
Gauge32
RO
Resettable Forward Active Energy counter.
epc1292ForwEnergyReactiveRe-
settable
.50.1.5.1.2.1.19.x
Gauge32
RO
Resettable Forward Reactive Energy counter.
epc1292RevEnergyActive
.50.1.5.1.2.1.20.x
Gauge32
RO
Reverse Active Energy counter.
epc1292RevEnergyReactive
.50.1.5.1.2.1.21.x
Gauge32
RO
Reverse Reactive Energy counter.
epc1292RevEnergyActiveReset-
table
.50.1.5.1.2.1.22.x
Gauge32
RO
Resettable Reverse Active Energy counter.
epc1292RevEnergyReactiveReset-
table
.50.1.5.1.2.1.23.x
Gauge32
RO
Resettable Reverse Reactive Energy counter.
epc1292OVPIndex
.50.1.5.2.1.1.x
Integer32
RO
None
epc1292OVPStatus
.50.1.5.2.1.2.x
INTEGER
RO
shows the status of the built-in Overvoltage Protection
epc1292SensorIndex
.50.1.6.1.1.1.x
Integer32
RO
None
epc1292TempSensor
.50.1.6.1.1.2.x
Integer32
RO
actual temperature
epc1292HygroSensor
.50.1.6.1.1.3.x
Integer32
RO
actual humidity
epc1292InputSensor
.50.1.6.1.1.4.x
INTEGER
RO
logical state of input sensor
epc1292AirPressure
.50.1.6.1.1.5.x
Integer32
RO
actual air pressure
epc1292DewPoint
.50.1.6.1.1.6.x
Integer32
RO
dew point for actual temperature and humidity
epc1292DewPointDiff
.50.1.6.1.1.7.x
Integer32
RO
difference between dew point and actual temperature (Temp -
DewPoint)
4.6
SSL
TLS Standard
The device is compatible with the standards TLSv1.0 to TLSv1.2. Due to lack of secur-
ity, SSLv3.0 as well as RC4 and DES encryptions are deactivated.