25
Expert Power Control 1202/1292
© 2018 Gude Analog- und Digitalsysteme GmbH
Operating
Account Credit: Credit: 130.50 Eur
2.4.1.1.3 Powerport: Advanced Switching (Batchmode)
Format
%port batchmode
[portnumber] [batch-sequence-number]
{Portcode/Mastercode}
[batch-sequence-number]
'11' .. '19' off, wait [t1 .. t9]s, on
'21' .. '29' on, wait [t1 .. t9]s, off
'31' .. '39' toggle, wait [t1 .. t9]s, toggle
Note
: Sequence numbers are identical to the DTMF codes for voice calls.
tn
Time in seconds
t1
1
t2
2
t3
5
t4
10
t5
20
t6
60
t7
120
t8
240
t9
480
Example:
%port batchmode
1 13
m0123
Answer:
Device name: epc007
Switch sequence: Port 1 off -> t3 -> on
Account Credit: Credit 130.50
2.4.1.1.4 Powerport: Advanced Switching (coldstart)
The command '
coldstart
' turns off all Powerports at once. Then it switches the ports
temporally delayed on again (according to the current power port configuration), as if
the device performs a cold start.
Format
%coldstart
{mastercode}
Example:
%coldstart
m0123
Answer:
Device name: epc007
Switch sequence: coldstart
Account Credit: Credit: 130.50 Eur