GST200-2 Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 45
Fig. 6-44
6.4.5 Customize
Entering number 5 in the screen in Fig. 6-35 will enter the customize screen, as shown
in Fig. 6-45.
Fig. 6-45
In this screen you can setup the output mode and PAS delay time.
6.4.5.1 Output Setup
Entering 1 in the screen of Fig. 6-45 will enter the screen for setting up output modes, as
in Fig. 6-46.
Fig. 6-46
Default Outputs
Selecting “1. Default Outputs” in the screen of Fig. 6-46 will set SOUNDER CIRCUIT
OUTPUT (Sounder A) on loop interface board and F.P.E. OUTPUT (F.P.E.) and the
zonal sounder to default output. That is, if any fire alarm comes,
If you have set the “Delay Mode” in Section 6.3.4.4 to “Disable”, Sounder A,
zonal sounder and F.P.E. will be automatically started.
If you have set the “Delay Mode” in Section 6.3.4.4 to “Enable”, Sounder A and
zonal sounder output after a 30-second delay, and F.P.E. immediately outputs.
C&E Outputs
*Zone Start Number*
Please Input 001
*Customize*
1. Outputs Setup
2. PAS Delay
3. Resound Configure
*Outputs Setup*
1.
Default Outputs
2.
C&E Outputs