GST200-2 Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 42
6.3.7.4 Exiting Test Mode for All Zones
Entering 4 in the screen shown in Fig. 6-31 will enter the screen for all zones to exit test
mode, as in Fig. 6-34.
Fig. 6-34
The screen for display a prompt before exit. After pressing
ENTER
for confirmation,
TEST MODE
indicator will go out.
6.4 Instructions for System Administrator (Manager Password
Required)
Press
SYSTEM
to enter the system setting screen. The screen is shown in Fig. 6-35.
Fig. 6-35
6.4.1 Modifying System Time
Entering “1” in the screen of Fig. 6-35, the system enters Time/Date setting screen, as
shown in Fig. 6-36. After Entering time at highlighted position and press
TAB
, then the
next cell is highlighted. Pressing
ENTER
will save the modification.
Fig. 6-36
6.4.2 Modifying Password
Entering “2” on the screen in Fig. 6-35, the system enters the window for password
modification, as in Fig. 6-37. Now the passwords can be modified.
*System Mode*
1
.
Time/Date
2
.
Password Change
3
.
Network Setup
4
.
Zone Start Number
5
.
Customize
6
.
Initialize System
7
.
Devices debug
* Time/Date Setting*
Please Input
Day Month Year
04 01 05
Hour Minute Sec
11 39 55
Stop All Zones Test
Press ENTER Confirm