GST200-2 Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 13
Description:
1. 20P data cable connecting with main board.
2. Red LED, which lights on receiving signals.
3. Green LED, which lights on sending signals.
4. RS485 network communication cable (A and B).
5. 20P data cable connecting with main board.
6. Standard RS232 interface connecting with GMC.
Note: You need to include an RS232 card in your first order of GST200-2 FACP.
Only with this card, device definition and C&E equations can be downloaded
from PC.
3.3 Peripheral Devices
3.3.1 A Series of Intelligent Fire Detectors
GST200-2 can connect with a series of fire detectors, such as I-9102, I-9103, and
I-9105R. The detectors mounted in the protected area transmit monitoring message to
the FACP through Class A loop. Every detector has its own address with which the
FACP can supervise the information of alarm, fault, and normal status of the detectors.
3.3.2 Modules
GST200-2 can connect with I-9300 Addressable Input Module and I-9301 Addressable
Single I/O Module. I-9300 module is used for receiving normally open digital signal from
fire protection devices and transmitting the signal back to the fire alarm control panel.
I-9301 module is for connecting fire protection devices that need to be controlled by the
FACP, such as smoke valve, fresh air valve, and damper valve. It can also receive
answer signal from these devices.
3.3.3 Loop Isolator
Loop Isolator can remove the shorted part of loop from the whole system to ensure
normal operation of other devices and to ascertain the location of the part in fault. After
the fault is repaired, the loop isolator can automatically reset the removed part into the
system.
3.3.4 Manual Call Points
A series of manual call points (such as I-9202) can be connected to the loop of
GST200-2. When fire is confirmed manually, pressing the glass on the MCP, alarm
signal can be sent to the FACP. After receiving the alarm signal, the FACP will show the
number and location of the MCP, and sound alarm.
3.3.5 Sounder Strobes
Summary of Contents for GST200-2
Page 1: ......