GST200-2 Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 39
shown in Fig. 6-26.
Fig. 6-26
In this screen, choosing “1 Zone Mode” can browse system messages by zone, and
choosing “2 Loop Mode” can browse by loop.
6.3.5.3 Printing Mode Setup
Entering 3 in the screen of Fig. 6-24 will enter the screen for setting up print mode, as
shown in Fig. 6-27.
Fig. 6-27
Entering number “1” means printing is disabled.
Entering number “2” means only printing fire alarm message.
Entering number “3” means printing the currently viewed message when checking
history records.
6.3.5.4 Positive Alarm Sequence (PAS) Setup
Entering 4 in the screen of Fig. 6-24 will enter the screen for setting up pre-alarm screen,
as shown in Fig. 6-28.
Fig. 6-28
If the panel is set to PAS mode enabled,
On receiving the first fire alarm from a detector,
PRE-ALARM
LED will illuminate.
The FACP generates fire alarm sound, and starts 15-second delay. The LCD
*Browse Mode*
1 Zone Mode
2 Loop Mode
*Print Mode*
1 Disable
2 Only Fire
3 All History
*PAS Mode*
1 Disable
2 Enable