GST200-2 Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 8
The display area consists of clock, LCD, LED and keypad, which are shown in Fig. 3-3.
Fig. 3-3
3.1.2 Description of LEDs
FIRE:
Red. It illuminates when the FACP detects an alarm condition of connected
detectors. After fire condition is removed, the fire status can only be cleared by
pressing
RESET
key, and this LED goes out simultaneously.
COMMON FAULT:
Yellow. It illuminates when the FACP detects fault of connected
devices or itself. It goes out automatically after the fault condition is removed.
DISABLED:
Yellow. It illuminates when any connected devices, zones or outputs
are disabled. It goes out when such status is canceled.
TEST MODE:
Yellow. It illuminates when any zone is in test mode. It goes out when
test mode is canceled.
POWER ON:
Green. It illuminates when the mains power or battery is normal.
SYSTEM FAULT:
Yellow. It illuminates if the program encounters a dead halt or the
system cannot work normally. After the fault condition is removed, only by pressing
RESET
, can system fault be cleared, and this LED goes out.
POWER FAULT:
Yellow. It illuminates when the mains power, battery or charger of
the FACP is in fault condition. It goes out when the fault is cleared.
F.P.E. FLT/DIS:
Yellow. It flashes when
F.P.E. output is in fault and illuminates
steadily after the F.P.E. output is disabled. It goes out after fault and disabled
conditions are cleared.
DELAY MODE:
Yellow, it illuminates when the output is set in delay mode. It goes
out when the delay mode is canceled.
SILENCE:
Yellow. It illuminates when the sounders are silenced. It goes out until a
new alarm comes, or the FACP is reset or
EVAC
key is pressed.
PRE-ALARM:
Red. It illuminates when there is pre-alarm message.