GST-M200 Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 26
PAS.
2. Defining modules
First enter the device code, press
ENTER
, the LCD indicates to input zone number.
Input the zone number of the device.
Pressing
TAB
to move the cursor to device type setting area for selecting device type
(for example, SMOKE (ION), refer to Table 3-1).
Selection of device type of detectors and monitor modules will affect the function of the
point as in Table 3-1:
Table 3-1
Device Type
No.
Action When Activated
Undefined
00
Undefined
SMOKE(ION)
01
Fire Alarm
SMOKE(PHOTO)
02
Fire Alarm
SMOKE-DUCT-P
03
Fire Alarm
HEAT DETECT
04
Fire Alarm
BEAM DETECT
05
Fire Alarm
PULL STATION
06
Fire Alarm
@\x0
07
Fire Alarm
@\x1
08
Fire Alarm
@\x2
09
Fire Alarm
@\x3
10
Fire Alarm
Waterflow
11
Fire Alarm
@\x4
12
Supervisory, latching
@\x5
13
Supervisory, latching
@\x6
14
Supervisory, latching
@\x7
15
Supervisory, latching
Supervisory
16
Supervisory, latching
Supervisory-AR
17
Supervisory, non latching (tracking)
@\x8
18
Supervisory, non latching (tracking)
Bell Circuit
19
Control Type
Horn Circuit
20
Control Type
Sounders
21
Control Type
Relay
22
Control Type
Strobe Circuit
23
Control Type
Control
24
Control Type
@\x9
25
Control Type