GST-M200 Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 23
for setting PAS delay time.
Fig. 3-9
System default delay time is 000, which can be set from 0~180 seconds.
3.4.1.5 User Defined SLC Type
This FACP supports 15 user-defined device types, which are from @\x0~@\xe in Table
3-1. With this option, the user can define those devices not included in the device type list.
Before defining devices for a specific project, the user needs to check whether all devices
for the project are in the device type list. If not, the device types not included should be
defined before starting device definition.
Selecting
“5. Defined SLC Type” in the screen of Fig. 3-3 will cause the following screen to
appear for user-definable SLC devices.
Fig. 3-10
To define an SLC device, the number of the user-defined device should be input, and then
its device type (Maximum 14 characters), like the
“Gas Detector” in the above example.
Please refer to Section 3.1 for how to edit the texts.
3.4.1.6 My Words
Selecting
“6. My Words” in the screen shown in Fig. 3-3, the following screen will appear:
* PAS Delay *
RANGE 0-180 SECONDS
Please Input: 000
* Defined SLC TYPE *
Please Input
SLC Type Num: 01
T [Gas Detector ]