GST-M200 Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 11
to commission.
The microprocessor disposes data by sampling and can save 14 history records.
The curve displayed on the FACP shows the field conditions.
Compensating excursion of temperature and humidity, detecting dust
accumulation fault.
Heat Detectors
I-9103(UL) / JTW-ZCD-G3N Intelligent Rate of Rise and Fixed Temperature Heat Detector
uses a thermistor as its sensor. The built-in microprocessor processes the signal from
the sensor by intelligent algorithm. The detector has the following features:
Addressable code is written by programmer.
The microprocessor disposes data by real-time sampling and can store 14
history records. The curve displayed on the FACP shows the field condition.
The detector can be set by programmer to be rate-of-rise detector or fixed
temperature detector.
Detector Bases
DZ-03 Base is used to mount conventional and intelligent smoke, heat and combination
detectors as their conductive base. During installation, you can easily fix the base before
connecting cables, and then twist the detector onto the base.
1.6.2 Manual Pull Stations
UL listed conventional manual pull stations can be connected through GST-LD-8300 /
I-M9300 Module to complete a fire alarm system.
1.6.3 Loop Isolators
In loop type fire alarm system, short circuit of part of the loop often affects normal
operation of the whole system. GST-LD-8322 / C-9503 / C-M9503 Loop Isolator can
disable the shorted part of loop from the whole system to ensure normal operation of other
parts and can easily find the location of the disabled part.
1.6.4 Control Modules
I-M9300 / GST-LD-8300 Addressable Input Module is used to receive normally open
switch signals from connected fire protection devices, and transmit the messages
back to the FACP.
I-M9301 / GST-LD-8301 Addressable Output Module works in two-wire mode. On
receiving start command from the FACP, it will close the output relay to output
normally-open / normally closed contact signal and illuminate the Active indicator.
1.6.5 Synchronization Module and Horn / Strobes Module
Synchronization Module: UL listed I56-0983-015R MDL Module manufactured by
System Sensor;
Horns/Strobes: UL listed P2475RLP, P2475RLPW manufactured by System Sensor.
NOTE:
If the FACP is to be connected with a synchronization module, the cables
between them are to be protected with metal conduits.
Summary of Contents for GST-M200
Page 1: ......