GST-M200 Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 10
ALARM SILENCE
key. Output can be silenced. The FACP will report
fault when connected cable is in short or open circuit or ground fault.
NAC2 (+, -): It outputs when there is fire alarm, which can be stopped by pressing
ALARM SILENCE
key. Output can be silenced. The FACP will report
fault when connected cable is in short or open circuit or ground fault.
Relays (For Common Use)
Three relay outputs are provided, controlling the fault, fire and supervisory state. Contact
capacity is 2.0A @ 30VDC (resistive).
ALARM (COM, NC, NO): The normally open contact closes if fire alarm condition
occurs and can be disconnected if the alarm is cleared.
FAULT (COM, NC, NO): The normally open contact closes if fault condition
occurs and can be disconnected if the fault resets.
Supervisory (COM, NC, NO): The normally open contact closes if abnormal
condition occurs and can be disconnected if the abnormal condition resets.
Auxiliary Power Output
24V, GND: Auxiliary 24VDC output.
EIA-485 Output: RS485 communication interface for networking. No connection, for
future use.
1.5 Components
A standard FACP consists of one of each of the following: main board, loop power
interface board.
Main Board: Main board is the core of the FACP, containing the system
’s CPU and
wiring interface with other main and optional components.
Loop Power Interface Board: Providing power for the main board and managing
battery charging. This is also the signal interface board for communication, detection,
fire alarm output and fault output, for the FACP to complete a fire alarm system with
all periphery devices.
1.6 Peripheral Devices
1.6.1 Series Addressable Detectors
Intelligent, addressable detectors provide information to the FACP on an SLC (Signaling
Line Circuit). This allows the FACP to continually monitor the status (alarm, trouble,
maintenance or normal) of each detector.
Smoke Detectors (Photoelectric)
I-9102(UL) / JTY-GD-G3 Intelligent Photoelectric Smoke Detector is developed on the
principle of infrared scattering. With integrated microprocessor and amplifier, the detector
has the following features:
Addressable code written by a programmer makes the detector easy and reliable
Summary of Contents for GST-M200
Page 1: ......