GST-M200 Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 25
3.4.3 Point Edit
3.4.3.1 Function
The
“Point Edit” option allows the operator to define the address, type, location, zone
number of a device. With these information defined, the operator can quickly find the
alarm zone and take timely measures in case of fire or trouble.
3.4.3.2 Basic Steps for Device Definition
Selecting
“2. Point Edit” in the screen in Fig. 3-2, the LCD will display the following:
Fig. 3-13
1. Defining detectors
First input detector code, then press
Enter
, the display will indicate to input zone
information.
Input the zone number.
Press
TAB
to move the cursor to device type area and select the type (such as
SMOKE (ION) as shown in Table 3-1). Note: If a detector is selected to be a SUPERV
DUCTP type, it will function like a supervisory point when it senses smoke. The
Supervisory LED and supervisory relay will be activated.
Press
TAB
to move to device description area, and input the text for describing the
device (32 characters at most). Please refer to Section 3.1 for how to edit the text.
Press
ENTER
, the state of Walk Test and PAS for this device will appear at the lower
part of the screen, of which
“0” means OFF and “1” means ON.
Walk Test
The walk test feature allows one person to test the system without manually resetting
the control panel after activation of a device. To enable a device for the walk test
feature, input number
“1”, the display is “ON”; To disable the walk test feature, input
number
“0”, the display changes to “OFF”.
Positive Alarm Sequence (PAS)
The Positive Alarm Sequence (PAS) option will program the detector to delay panel
activation (including alarm relay) for a period of 15 seconds plus a programmable
time of up to 3 minutes. To enable a device for the PAS feature, input number
“1”, the
display changes to
“ON”; To disable the PAS feature, input number “0”, the display
changes to
“OFF”. Please refer to Section 4.9 for detailed operation procedure of
Code: 005 @ Zone: 001
Type: 01 SMOKE (ION)
1 [ Floor1 Office1
]
Walk Test:--------------------1 ON
PAS:---------------------------0 OFF