9.11 Pump 4 register block
All register values are read-only, and 0xFFFF indicates that the
data value is not available.
Unless otherwise stated, the data type used for counters and
scaled values is always an unsigned integer.
Address Register name
Scale
Description
00551
Pump4.MotorTemperature
0.01 K
Motor temperature, pump 4.
00552
Pump4.ElectronicTemperature
0.01 K
Electronics temperature, pump 4.
00553
Pump4.AverageLineVoltage
0.1 V
Average supply voltage, pump 4.
00554
Pump4.AverageLineCurrent
0.1 A
Average supply current, pump 4.
00555
Pump4.AverageLineCurrentLatest
0.1 A
Average supply current the last time pump 4 was
operating.
00556
Pump4.LineFrequency
0.1 Hz
Frequency of power supply, pump 4.
00557
Pump4.PhaseSequence
Bool
Phase sequence of power supply, pump 4.
00558
Pump4.CosPhi
0.01
Power factor, pump 4.
00559
Pump4.Power
1 W
Power consumption, pump 4.
00560
00561
Pump4.EnergyTripCounterHI
Pump4.EnergyTripCounterLO
1 kWh
Energy consumption, pump 4.
Can be reset with register 00101, bit 5:
PitPump4ResetHistory.
00562
Pump4.WaterLevel
0.01 m
Water level as estimated by pump 4.
00563
Pump4.WaterLevelMax
0.01 m
Logged maximum value of water level, pump 4.
Can be reset with register 00101, bit 5:
PitPump4ResetHistory.
00564
Pump4.MaxContinousTime
1 minute
Logged maximum value of continuous operating time
within the last 30 days, pump 4.
Can be reset with register 00101, bit 5:
PitPump4ResetHistory.
00565
00566
Pump4.TotalPoweredTimeHI
Pump4.TotalPoweredTimeLO
1 minute
Total time that pump 4 has been powered on.
Used as time stamp for alarms in the alarm log the
moment the alarm appears.
00567
00568
Pump4.OperationTimeHI
Pump4.OperationTimeLO
1 minute
Total time that pump 4 has been operating.
00569
00570
Pump4.OperationTimeTripCounterHI
Pump4.OperationTimeTripCounterLO
1 minute
Trip counter of the total time that pump 4 has been
operating.
Can be reset with register 00101, bit 5:
PitPump4ResetHistory.
00571
00572
Pump4.NumberOfStartsHI
Pump4.NumberOfStartsLO
Unscaled
Total number of starts, pump 4.
00573
00574
Pump4.NumberOfStartsTripCounterHI
Pump4.NumberOfStartsTripCounterLO
Unscaled
Trip counter of total number of starts, pump 4.
00575
Pump4.AlarmCode
Unscaled
Grundfos-specific alarm code, pump 4.
See section
.
00576
Pump4.WarningCode
Unscaled
Grundfos-specific warning code, pump 4.
See section
.
00577
Pump4.OperatingMode
Bits
Operating mode of pump 4.
0: "Auto" mode (power-on default)
1: Forced start
2: Forced stop.
00528
Bit 0: Subpump4AlarmsPhaseSequence
Phase sequence reversed
Bit 1: Subpump4AlarmsOvervoltage
Overvoltage
Bit 2: Subpump4AlarmsUndervoltage
Undervoltage
Bit 3: Subpump4AlarmsOverload
Overload
Bit 4: Subpump4AlarmsBlockedMotor
Blocked motor or pump
Bit 5: Subpump4AlarmsAlarmBit5
-
Bit 6: Subpump4AlarmsMotorTemperature
Motor temperature
Bit 7: Subpump4AlarmsElectronicTemperature
Temperature, control electronics
Bit 8: Subpump4AlarmsTermoRelay1
Temperature relay 1 in motor, for example Klixon
Bit 9: Subpump4AlarmsTermoRelay2
Temperature relay 2 in motor, for example thermistor
Bit 10: Subpump4AlarmsVerificationError
Verification error, code area (ROM, FLASH)
Bit 11: Subpump4AlarmsAlarmBit11
-
Bit 12: Subpump4AlarmsSensorFault
Sensor fault
Bit 13: Subpump4AlarmsAlarmBit13
-