13.11 Reset alarm
This section shows how to reset an alarm. In the example, slave
address 0x01 (1) is used. The ResetAlarm is the first bit in
register 00101, so the bit must be set from 0 to 1.
Request from master to slave
Example of response from slave to master
If there is no response from the slave, see section
Field
Value
Description
Slave address
0x01
-
Function code
0x06
Write single register
Start address HI
0x00
ControlRegister address:
00101 (0x0065)
Start address LO
0x64
-
Value HI
0x00
Set the value to 1.
Value LO
0x01
-
Field
Value
Description
Slave address
0x01
-
Function code
0x06
Write single register
Start address HI
0x00
ControlRegister address:
00101 (0x0065)
Start address LO
0x64
-
Value HI
0x00
Set the value to 1.
Value LO
0x01
-