English (GB)
14
7.3 Setting up the IP addresses
The CIM 500 ethernet module is default set to a fixed IP address.
It is possible to change the IP address settings from the built-in
webserver.
7.4 Establish connection to the webserver
You can configure the CIM 500 module using the built-in
webserver. To establish a connection from a PC to CIM 500, the
following steps are required:
• Connect the PC and the CIM 500 module using an ethernet
cable
• Configure the PC ethernet port to the same subnetwork as
CIM 500, for example 192.168.1.101, and the subnet mask to
255.255.255.0. See section
.
• Open a standard Internet browser and type 192.168.1.100 in
the URL field.
• Log in to the webserver using the following:
Fig. 17
CIM 500 connected to PC via ethernet cable
For further information on how to use the webserver, see section
on page
.
7.5 Status LEDs
The CIM 500 ethernet module has two Status LEDs: LED1 and
LED2. See fig.
• Red and green status LED1 for ethernet communication
• Red and green status LED2 for internal communication
between CIM 500 and the Grundfos product.
LED1
LED2
7.6 DATA and LINK LEDs
The CIM 500 ethernet module has two connectivity LEDs related
to each RJ45 connector. See fig.
DATA1 and DATA2
These yellow LEDs indicate data traffic activity.
LINK1 and LINK2
These green LEDs shows whether the ethernet cable is properly
connected.
Default IP settings
used by the
webserver
IP address:
192.168.1.100
Subnet mask: 255.255.255.0
Gateway: 192.168.1.1
IP settings for
Modbus TCP
Configure the settings via the webserver.
User name
admin (default)
Password
Grundfos (default)
User name and password may have been changed
from their default values.
TM
05
64
36
47
12
You can use both ETH1 and ETH2 to establish a
connection to the webserver.
You can access the webserver while the selected
Industrial protocole is active.
Status
Description
Off
No Modbus TCP communication or
switched off.
Flashing green
Modbus TCP communication active.
Permanently red
CIM 500 module configuration fault. See
section
Permanently red and
green
Error in the firmware download. See
section
Flashing red and
green
Resetting to factory default.
After 20 seconds, CIM 500 restarts.
Status
Description
Off
CIM 500 is switched off.
Flashing red
No internal communication between CIM
500 and the CIU 502 unit.
Permanently red
CIM 500 does not support the Grundfos
product connected.
Permanently green
Internal communication between CIM
500 and CIU 502 is OK.
Permanently red and
green
Memory fault.
During startup, there is a delay of up to 5 seconds
before LED1 and LED2 status is updated.
Status
Description
Yellow off
No data communication on the RJ45 connector.
Yellow
flashing
Data communication ongoing on the RJ45
connector.
Permanently
yellow
Heavy network traffic on the RJ45 connector.
Status
Description
Green off
No ethernet Link on the RJ45 connector.
Green on
Ethernet Link on the RJ45 connector is OK.