English (GB)
24
Bit 10:
PitPump1PumpDownAck
Bool
Indicates if a PitPump1PumpDown control bit is acknowledged by the
device.
This bit is only active if AutoAckControlBits (register 00005, bit 0) is set
to "0".
0: Not acknowledged
1: Acknowledged.
Bit 11:
PitPump2PumpDownAck
Bool
Indicates if a PitPump2PumpDown control bit is acknowledged by the
device.
This bit is only active if AutoAckControlBits (register 00005, bit 0) is set
to "0".
0: Not acknowledged
1: Acknowledged.
Bit 12:
PitPump3PumpDownAck
Bool
Indicates if a PitPump3PumpDown control bit is acknowledged by the
device.
This bit is only active if AutoAckControlBits (register 00005, bit 0) is set
to "0".
0: Not acknowledged
1: Acknowledged.
Bit 13:
PitPump4PumpDownAck
Bool
Indicates if a PitPump4PumpDown control bit is acknowledged by the
device.
This bit is only active if AutoAckControlBits (register 00005, bit 0) is set
to "0".
0: Not acknowledged
1: Acknowledged.
00202
Bit 0:
AlarmInPumpOrPit
Bool
Main status of warning(s).
0: No active warnings.
1: One or more active warnings.
Bit 1:
WarningInPumpOrPit
Bool
Main status of alarm(s).
0: No active alarms.
1: One or more active alarms.
Bit 2:
ManualControlStatus
Bool
Main status of manual pump control.
0: No manual pump control enabled (full "Auto")
1: Manual pump control enabled (partly or completely).
Bit 3: RESERVED
-
-
00203
PitMode
Enum
Pit mode.
0: Single-pit mode
1: Multi-pit mode.
See section
10.4 Single-pit and multi-pit mode
00204
SinglePitStopLevel
0.01 m
Stop level, pit. Used in single-pit mode only.
Pit mode: 0. Pit mode is set in register 00203.
00205
SinglePitStartLevelMax
0.01 m
Start level max., pit. Used in single-pit mode only.
Pit mode: 0. Pit mode is set in register 00203.
00206
SinglePitStartLevelBand
0.01 m
Start level band, pit. Used in single-pit mode only.
Pit mode: 0. Pit mode is set in register 00203.
00207
SinglePitHighWaterLevel
0.01 m
High water level, pit. Used in single-pit mode only.
Pit mode: 0. Pit mode is set in register 00203.
00208
MultiPitPump1StopLevel
0.01 m
Stop level, pump 1. Used in multi-pit mode only.
Pit mode: 1. Pit mode is set in register 00203.
00209
MultiPitPump1StartLevelMax
0.01 m
Start level max., pump 1. Used in multi-pit mode only.
Pit mode: 1. Pit mode is set in register 00203.
00210
MultiPitPump1StartLevelBand
0.01 m
Start level band, pump 1. Used in multi-pit mode only.
Pit mode: 1. Pit mode is set in register 00203.
00211
MultiPitPump1HighWaterLevel
0.01 m
Actual high water level, pump 1. Used in multi-pit mode only.
Pit mode: 1. Pit mode is set in register 00203.
00212
MultiPitPump2StopLevel
0.01 m
Stop level, pump 2. Used in multi-pit mode only.
Pit mode: 1. Pit mode is set in register 00203.
00213
MultiPitPump2StartLevelMax
0.01 m
Start level max., pump 2. Used in multi-pit mode only.
Pit mode: 1. Pit mode is set in register 00203.
00214
MultiPitPump2StartLevelBand
0.01 m
Start level band, pump 2. Used in multi-pit mode only.
Pit mode: 1. Pit mode is set in register 00203.
00215
MultiPitPump2HighWaterLevel
0.01 m
High water level, pump 2. Used in multi-pit mode only.
Pit mode: 1. Pit mode is set in register 00203.
00216
MultiPitPump3StopLevel
0.01 m
Stop level, pump 3. Used in multi-pit mode only.
Pit mode: 1. Pit mode is set in register 00203.
00217
MultiPitPump3StartLevelMax
0.01 m
Start level max., pump 3. Used in multi-pit mode only.
Pit mode: 1. Pit mode is set in register 00203.
00218
MultiPitPump3StartLevelBand
0.01 m
Start level band, pump 3. Used in multi-pit mode only.
Pit mode: 1. Pit mode is set in register 00203.
Address
Register name
Scale
Description