English (GB)
28
9.8 Pump 1 register block
All register values are read-only, and 0xFFFF indicates that the
data value is not available.
Unless otherwise stated, the data type used for counters and
scaled values is always an unsigned integer.
Address Register name
Scale
Description
00401
Pump1.MotorTemperature
0.01 K
Motor temperature, pump 1.
00402
Pump1.ElectronicTemperature
0.01 K
Electronics temperature, pump 1.
00403
Pump1.AverageLineVoltage
0.1 V
Average supply voltage, pump 1.
00404
Pump1.AverageLineCurrent
0.1 A
Average supply current, pump 1.
00405
Pump1.AverageLineCurrentLatest
0.1 A
Average supply current the last time pump 1 was
operating.
00406
Pump1.LineFrequency
0.1 Hz
Frequency of power supply, pump 1.
00407
Pump1.PhaseSequence
Bool
Phase sequence of power supply, pump 1.
00408
Pump1.CosPhi
0.01
Power factor, pump 1.
00409
Pump1.Power
1 W
Power consumption, pump 1.
00410
00411
Pump1.EnergyTripCounterHI
Pump1.EnergyTripCounterLO
1 kWh
Energy consumption, pump 1.
Can be reset with register 00101, bit 2:
PitPump1ResetHistory.
00412
Pump1.WaterLevel
0.01 m
Water level as estimated by pump 1.
00413
Pump1.WaterLevelMax
0.01 m
Logged maximum value of water level, pump 1.
Can be reset with register 00101, bit 2:
PitPump1ResetHistory.
00414
Pump1.MaxContinousTime
1 minute
Logged maximum value of continuous operating time
within the last 30 days, pump 1.
Can be reset with register 00101, bit 2:
PitPump1ResetHistory.
00415
00416
Pump1.TotalPoweredTimeHI
Pump1.TotalPoweredTimeLO
1 minute
Total time that pump 1 has been powered on.
Used as time stamp for alarms in the alarm log the
moment the alarm appears.
00417
00418
Pump1.OperationTimeHI
Pump1.OperationTimeLO
1 minute
Total time that pump 1 has been operating.
00419
00420
Pump1.OperationTimeTripCounterHI
Pump1.OperationTimeTripCounterLO
1 minute
Trip counter of the total time that pump 1 has been
operating.
Can be reset with register 00101, bit 2:
PitPump1ResetHistory.
00421
00422
Pump1.NumberOfStartsHI
Pump1.NumberOfStartsLO
Unscaled
Total number of starts, pump 1.
00423
00424
Pump1.NumberOfStartsTripCounterHI
Pump1.NumberOfStartsTripCounterLO
Unscaled
Trip counter of total number of starts, pump 1.
00425
Pump1.AlarmCode
Unscaled
Grundfos-specific alarm code, pump 1.
See section
00426
Pump1.WarningCode
Unscaled
Grundfos-specific warning code, pump 1.
See section
00427
Pump1.OperatingMode
Bits
Operating mode of pump 1.
0: "Auto" mode (power-on default)
1: Forced start
2: Forced stop.
00428
Bit 0: Subpump1AlarmsPhaseSequence
Phase sequence reversed
Bit 1: Subpump1AlarmsOvervoltage
Overvoltage
Bit 2: Subpump1AlarmsUndervoltage
Undervoltage
Bit 3: Subpump1AlarmsOverload
Overload
Bit 4: Subpump1AlarmsBlockedMotor
Blocked motor/pump
Bit 5: Subpump1AlarmsAlarmBit5
-
Bit 6: Subpump1AlarmsMotorTemperature
Motor temperature
Bit 7: Subpump1AlarmsElectronicTemperature
Temperature, control electronics
Bit 8: Subpump1AlarmsTermoRelay1
Temperature relay 1 in motor, for example Klixon
Bit 9: Subpump1AlarmsTermoRelay2
Temperature relay 2 in motor, for example thermistor
Bit 10: Subpump1AlarmsVerificationError
Verification error, code area (ROM, FLASH)
Bit 11: Subpump1AlarmsAlarmBit11
-
Bit 12: Subpump1AlarmsSensorFault
Sensor fault
Bit 13: Subpump1AlarmsAlarmBit13
-