Bit 9: PitPump4ResetAlarm
Bool
Control bit that resets alarms and warnings from pump 4.
0: No resetting
1: Resetting alarm.
This control bit is triggered on rising edge only, meaning setting logical 0 to
1.
See section
9.2 CIM configuration register block
, address 00005, for
acknowledgement behaviour.
Bit 10: PitPump1PumpDown
Bool
Control bit that starts pump 1 as if the level control has started it, and
pump 1 will pump down the water level and then be stopped by the level
control.
0: No pumping
1: Pump down.
This control bit is triggered on rising edge only, meaning setting logical 0 to
1.
See section
9.2 CIM configuration register block
, address 00005, for
acknowledgement behaviour.
Bit 11: PitPump2PumpDown
Bool
Control bit that starts pump 2 as if the level control has started it, and
pump 2 will pump down the water level and then be stopped by the level
control.
0: No pumping
1: Pump down.
This control bit is triggered on rising edge only, meaning setting logical 0 to
1.
See section
9.2 CIM configuration register block
, address 00005, for
acknowledgement behaviour.
Bit 12: PitPump3PumpDown
Bool
Control bit that starts pump 3 as if the level control has started it, and
pump 3 will pump down the water level and then be stopped by the level
control.
0: No pumping
1: Pump down.
This control bit is triggered on rising edge only, meaning setting logical 0 to
1.
See section
9.2 CIM configuration register block
, address 00005, for
acknowledgement behaviour.
Bit 13: PitPump4PumpDown
Bool
Control bit that starts pump 4 as if the level control has started it, and
pump 4 will pump down the water level and then be stopped by the level
control.
0: No pumping
1: Pump down.
This control bit is triggered on rising edge only, meaning setting logical 0 to
1.
See section
9.2 CIM configuration register block
, address 00005, for
acknowledgement behaviour.
00102
SetSinglePitStopLevel
0.01 m
Setting of stop level, pit. Used in single-pit mode only.
Pit mode: 0. Pit mode is set in register 00203.
00103
SetSinglePitStartLevelMax
0.01 m
Setting of start level max., pit. Used in single-pit mode only.
Pit mode: 0. Pit mode is set in register 00203.
00104
SetSinglePitStartLevelBand
0.01 m
Setting of start level band, pit. Used in single-pit mode only.
Pit mode: 0. Pit mode is set in register 00203.
00105
SetSinglePitHighWaterLevel
0.01 m
Setting of high water level, pit. Used in single-pit mode only.
Pit mode: 0. Pit mode is set in register 00203.
00106
SetMultiPitPump1StopLevel
0.01 m
Setting of stop level, pump 1. Used in multi-pit mode only.
Pit mode: 1. Pit mode is set in register 00203.
00107
SetMultiPitPump1StartLevelMax
0.01 m
Setting of start level max., pump 1. Used in multi-pit mode only.
Pit mode: 1. Pit mode is set in register 00203.
00108
SetMultiPitPump1StartLevelBand
0.01 m
Setting of start level band, pump 1. Used in multi-pit mode only.
Pit mode: 1. Pit mode is set in register 00203.
00109
SetMultiPitPump1HighWaterLevel 0.01 m
Setting of high water level, pump 1. Used in multi-pit mode only.
Pit mode: 1. Pit mode is set in register 00203.
00110
SetMultiPitPump2StopLevel
0.01 m
Setting of stop level, pump 2. Used in multi-pit mode only.
Pit mode: 1. Pit mode is set in register 00203.
00111
SetMultiPitPump2StartLevelMax
0.01 m
Setting of start level max., pump 2. Used in multi-pit mode only.
Pit mode: 1. Pit mode is set in register 00203.
00112
SetMultiPitPump2StartLevelBand
0.01 m
Setting of start level band, pump 2. Used in multi-pit mode only.
Pit mode: 1. Pit mode is set in register 00203.
00113
SetMultiPitPump2HighWaterLevel 0.01 m
Setting of high water level, pump 2. Used in multi-pit mode only.
Pit mode: 1. Pit mode is set in register 00203.
00114
SetMultiPitPump3StopLevel
0.01 m
Setting of stop level, pump 3. Used in multi-pit mode only.
Pit mode: 1. Pit mode is set in register 00203.
Address
Register name
Scale
Description