9.5 Pit control and configuration register block
Registers in this block can be read by means of function codes
0x03 and/or 0x04. They can be written as holding registers with
function code 0x06 and 0x10.
Unless otherwise stated, the data type used for counters and
scaled values is always an unsigned integer.
Address
Register name
Scale
Description
00101
Bit 0: ResetAlarm
Bool
Control bit that resets system alarms and warnings.
0: No resetting
1: Resetting alarm.
This control bit is triggered on rising edge only, meaning setting logical 0 to
1.
See section
9.2 CIM configuration register block
, address 00005, for
acknowledgement behaviour.
Bit 1: ResetHistory
Bool
Control bit that resets pit history.
0: No resetting
1: Resetting history.
This control bit is triggered on rising edge only, meaning setting logical 0 to
1.
See section
9.2 CIM configuration register block
, address 00005, for
acknowledgement behaviour.
Bit 2: PitPump1ResetHistory
Bool
Control bit that resets counters in pump 1.
0: No resetting
1: Resetting history.
This control bit is triggered on rising edge only, meaning setting logical 0 to
1.
See section
9.2 CIM configuration register block
, address 00005, for
acknowledgement behaviour.
Bit 3: PitPump2ResetHistory
Bool
Control bit that resets counters in pump 2.
0: No resetting
1. Resetting history.
This control bit is triggered on rising edge only, meaning setting logical 0 to
1.
See section
9.2 CIM configuration register block
, address 00005, for
acknowledgement behaviour.
Bit 4: PitPump3ResetHistory
Bool
Control bit that resets counters in pump 3.
0: No resetting
1: Resetting history.
This control bit is triggered on rising edge only, meaning setting logical 0 to
1.
See section
9.2 CIM configuration register block
, address 00005, for
acknowledgement behaviour.
Bit 5: PitPump4ResetHistory
Bool
Control bit that resets counters in pump 4.
0: No resetting
1: Resetting history.
This control bit is triggered on rising edge only, meaning setting logical 0 to
1.
See section
9.2 CIM configuration register block
, address 00005, for
acknowledgement behaviour.
Bit 6: PitPump1ResetAlarm
Bool
Control bit that resets alarms and warnings from pump 1.
0. No resetting
1: Resetting alarm.
This control bit is triggered on rising edge only, meaning setting logical 0 to
1.
See section
9.2 CIM configuration register block
, address 00005, for
acknowledgement behaviour.
Bit 7: PitPump2ResetAlarm
Bool
Control bit that resets alarms and warnings from pump 2.
0: No resetting
1: Resetting alarm.
This control bit is triggered on rising edge only, meaning setting logical 0 to
1.
See section
9.2 CIM configuration register block
, address 00005, for
acknowledgement behaviour.
Bit 8: PitPump3ResetAlarm
Bool
Control bit that resets alarms and warnings from pump 3.
0: No resetting
1: Resetting alarm.
This control bit is triggered on rising edge only, meaning setting logical 0 to
1.
See section
9.2 CIM configuration register block
, address 00005, for
acknowledgement behaviour.