Cleaning, inspection, maintenance
53 | 76
BA_TD
3-
BS
00
0en
_07
4_sof
tli
Q
-S
C
.docx
11.
Read off the regeneration counter.
12.
Read off the soft water meter.
13.
Read out the error memory (Information 245).
Maintenance work
14.
Check the hose connections for leaks and damage.
15.
Check the soft water meter for pulse output (current flow rate during operation,
refer to Info level 2).
16.
Check all cables and connections for damage and a firm seat.
17.
Check the injector and the injector sieve for impurities and clean them, if required.
18.
Check the brine filling orifice in the brine connection angle (red).
19.
Check the brine valve and the level electrodes and clean them, if necessary.
20.
Clean the brine tank.
21.
Initiate a manual regeneration.
22.
Check the suction power of the injector.
23.
Check the chlorine current during salting (regeneration step 2) (Code 245).
24.
Check the function of the regeneration counter during backwash by monitoring Info
level 3.
25.
Check the control valve at the drain outlet (flushing water hose, brine water hose)
in operating position for leaks.
26.
Check the filling and suction hoses to the brine valve for leaks.
27.
Reset the service interval, if activated.
28.
Record data and work performed, including repair work, in the operation log and
checklist.
29.
Hand over the water softener and the operation log to the owner/user.
8.4
Consumables
NOTE:
Danger of damaging the system if unsuitable consumables are used.
● Risk of functional impairment, malfunctions and loss of warranty.
► Only use genuine consumables.
Product
Order no.
Regeneration salt tablets (25 kg) acc. to EN 973 type A.
127 001
Water test kit "Total hardness“
170 187
Summary of Contents for softliQ:SC
Page 1: ...We understand water Water softener softliQ SC Operation manual...
Page 72: ...Notes 72 76 Notes...
Page 75: ......