Mobile reverse osmosis system
AVRO-flex 400
Order no. 095 752 946-inter Edited by: phar-mrie G:\BA-752946-INTER_095_AVRO-FLEX_400.DOCX
42
H Maintenance and care
1 | Basic information
In order to guarantee the reliable function of the systems over a long
period of time, some maintenance work has to be performed at regu-
lar intervals. All regulations and guidelines which apply at the installa-
tion site must be strictly adhered to.
Check the quality and the system volume flows every day.
Maintenance has to be performed by Grünbeck’s technical ser-
vice/authorised service company or by a specialised company.
Maintenance is subject to the load but at the latest has to be per-
formed once a year.
An operation log and the corresponding test log must be kept in or-
der to document the maintenance work performed.
Note:
By concluding a maintenance contract you ensure that all
maintenance work will be performed in due time.
The maintenance work performed must be documented in the check-
list, refer to appendix "Operation log".
2 | Inspection (functional check)
You may perform the daily inspections yourself.
Please refer to the following summary for the tasks to be performed
within the framework of an inspection.
Summary: Inspection work
Read the recovery
Note:
Minor deviations are normal and cannot be prevented techni-
cally. In case of considerable deviations from the standard, notify
Grünbeck's technical service.
Take the remaining time of the AVRO treatment unit’s maintenance
interval into consideration (refer to Chapter F, paragraph 2.1). If the
remaining time is < 100 hours, notify Grünbeck’s technical service/
authorised service company to have the treatment module re-
placed.
Take the remaining time of the maintenance interval [d] into consid-
eration (refer to Chapter F - paragraph 2.1 “Reading the operating
state”). In case the remaining time of the maintenance interval is <
30 days, inform Grünbeck's technical service about the impending
service.