Mobile reverse osmosis system
AVRO-flex 400
Order no. 095 752 946-inter Edited by: phar-mrie G:\BA-752946-INTER_095_AVRO-FLEX_400.DOCX
28
2.3 Workshop mode
To prevent damage to the membrane due to germs (bio-fouling), the
mobile reverse osmosis system AVRO-flex 400 must be run in work-
shop mode during the entire periods of standstill (refer to fig. E-3). In
this case, the permeate line as well as the concentrate line are con-
nected as per DIN EN 1717. In the workshop mode, water is rejected
for a certain time set in the controller (factory setting 15 min.) every
day.
Note:
The system must be connected to the power supply as well as
to the water/waste water network for the entire period of standstill
(transports up to 48 h excluded).
Note:
If installed, the shut-off valve on the permeate side must be
open!
BOXER
KD
Mobile reverse osmosis system AVRO-flex 400
Euro system separator GENO-DK 2-Mini
Fig. E-3: Installation drawing of mobile reverse osmosis system AVRO-flex 400 - workshop mode
1
3
2
Off
Workshop Filling
mode