Malfunction (error shown on LCD / LED)

  

  

“Normal“  operating  mode

:  Lubricus  Controller  display  „ON”  each  LED  for  activated  pumps  blink  shortly  one  after  each 

other in 1 second intervals. Not activated Lubricus Controller exits will not blink 
 

Example: 
Lubricus Controller exit 1: Lubricus LUB-C-2:    Adjustment green LED / left Lubricus body:  

2 exits = A02 

                                                                 

Adjustment orange LED / right Lubricus body:   0 exits = A00 

Lubricus Controller exit 2: Lubricus LUB-C1-1:  Adjustment green LED / left Lubricus body:  

1 exit = A01 

                                                                  

Adjustment orange LED / right Lubricus body:   1 exit = A01 

 

 

Green LED for normal operating mode is always illuminated, LED’s of Lubricus Controller exit  1 and 2 blink shortly one after 
each (green, green ,orange , and starting again from the beginning  …)

 

            

 

Error messages / faults

: The dedicated error message for each connected Lubricus unit is displayed. 

 

E1

Empty lubricant reservoir

: red LED lights cons Display will show error for Lubricus unit connected to Lubricus 

Controller exit + E1, when the sequence of the connected pump with the error is reached. If the sequence reaches the units 

without error the display will show “ON”, the red LED will still light to signal that an error message exists.  

Root cause:  

The lubricant cartridge is empty. The unit continues to be active and will pump! 

Corrective action:   replace cartridge. Lubricus will continue to run as per active program. 

Example:                  exit 1, Lubricus LUB-C-2, all OK                               exit 2, Lubricus LUB-C-1-1, cartridge empty 

                             

           

 

       

 

E2

Back pressure too high

red LED lights cons Display will show error for Lubricus unit connected to Lubricus 

Controller exit + E2; the error message is related to the Lubricus body half respectively to the Lubricus exit. 

 

Root cause:  

Back pressure was measured 3 x too high. The lubrication point could be clocked, the tube length could 

be too long or the grease is too stiff or has hardened. Lubricus will stop!  

Corrective action:   Trace reason for high back pressure >70bar and correct it.  

Switch unit „OFF“ and „On“ again. The error message will be reset to 0. Lubricus will start again as per 
program in memory. 

 Example:  

Exit 2, Lubricus LUB-C-1-1, Error 2E2 at exit 2 + orange LED / right Lubricus body half: exit1 

 

                  

 

Summary of Contents for Lubricus LUB-C-1

Page 1: ...User Guide Lubricus Controller LUB C 1 LUB C 2 LUB C 3 LUB C 4 LUB C 1 1 24 VDC Lubricus Type C...

Page 2: ...11 12 Activation of exits Pump specific adjustment 10 12 Inputting the generation of the Lubricus C devices used 13 Table pause time adjustments 14 Table quantity adjustment 14 Details Activation Sta...

Page 3: ...e installed in a central location Depending on the configuration of Lubricus Lubrication System Type C is available with up to four outlets and therefore suitable to lubricate several lubrication poin...

Page 4: ...the clear housing to remove the key for Setup or Adjustments of your Lubricus Simply turn clockwise to release key The point of the key is used for programming Please note Always replace the key for...

Page 5: ...ccessories and by observation of all installation operation and maintenance instructions Gr tzner GmbH excludes all liability if these instructions are not observed Gr tzner GmbH grants guarantees con...

Page 6: ...directly on the machine must be strictly followed and maintained in completely readable condition Qualification and training of the personnel The operation maintenance service and installation personn...

Page 7: ...th the manufacturer Original spare parts and accessories authorized by the manufacturer are for safety purposes Using other parts results in loss of liability for claims resulting out of this For comp...

Page 8: ...al connection Have the electric power supply connected only by a trained electrician Connection and wiring of the electric components should be done by an expert trained in this field Check the voltag...

Page 9: ...stallation Lubricus Controller settings Observe the safety instructions The programming mode enables Lubricus will be installed near the lubrication point Entering the quantity of exits per Lubricus I...

Page 10: ...page 10 Adjustment Flow chart...

Page 11: ...exit activated A01 1 exit activated A02 2 exits activated Settings for every specific Lubricus Models Type LUB C 1 adjustment at green LED left Lubricus body 1 exit A01 adjustment at orange LED right...

Page 12: ...Lubricus body 2 outlets is dispensing equal quantity Typ LUB C 4 adjustment at green LED left Lubricus body 2 exits A02 adjustment at orange LED right Lubricus body 2 exits A02 Left and right side of...

Page 13: ...parameter on the controller as all Lubricus controllers with n01 r03 software are set to the PU2 generation on delivery In accordance with this Pu2 is shown on the display After approx 4 seconds the d...

Page 14: ...bricus 1 side of body H Pause Time adjustment Time between 2 lubrication intervals 1 to 96 h possible H Pause Time hours 1 12 24 48 96 Result Lubrication cycles per exit per month 720 60 30 15 7 5 Int...

Page 15: ...orange LED Lubricus unit 2 green LED than orange LED Lubricus unit 3 green LED than orange LED Lubricus unit 4 green LED than orange LED Basic settings all Controller exits are not activated 3 After d...

Page 16: ...tment at green LED left side of Lubricus body 2 Exits A02 Touch sensor shortly with programming key until required information is displayed If there is no change the displayed value will be used After...

Page 17: ...es from 15 This is accurate enough to establish the condition of the lubrication point 5 Additional functions QuickCheck extra dispensing cycle pumping of small amounts of lubricant for testing purpos...

Page 18: ...when the sequence of the connected pump with the error is reached If the sequence reaches the units without error the display will show ON the red LED will still light to signal that an error message...

Page 19: ...nnected units will dispense as per program in memory Corrective action Change or connect cable broken missing or disconnected connection cable Switch unit OFF and On again The error message will be re...

Page 20: ...Imax approx 350 mA during pump operation typically 200 mA Standby current standby mode 20 mA Input Signal can switches ON and OFF PIN 2 no assignment PIN 3 Ground GND PIN 4 High operating mode OK inpu...

Page 21: ...serve the safety instructions Switch off Lubricus Controller 2 Take out ventilation locking turn clock wise to OPEN 3 Press the housing turn left and remove it 4 Remove the empty cartridge 5 Remove pr...

Page 22: ...rror report will be deleted Technical Data Lubricus Controller Control micro processor controlled up to 4 Lubricus units Type C can be connected Power supply 24 VDC Power consumption max 300mA typical...

Page 23: ...m outside and 4mm inside diameter Operating pressure max 70 bar Operating temperature 20 C to 80 C Dimensions max Width x height x depth 112 x 196 x 94 mm Weight without lubricant 1120g Control Lubric...

Page 24: ...age 24 Mounting Lubricus unit 2 srews 6mm for example M6x40 are required for a safe installation of your Lubricus The optimum clamping force of the screw is 5 Nm 3 points at the back assure a safe hol...

Page 25: ...re vs to tube length tested with tubes 6 x 4 mm Disposal When disposing lubricant the waste disposal instructions of the lubricant manufacturer must be observed Disposal of Lubricus Lubrication System...

Reviews: