DC Inverter Side Discharge VRF
Ⅱ
for North America
82
working, charge additional R410a with specific amount to the unit through the filling
opening of the liquid pipe valve of the outdoor unit. If required amount cannot be quickly
filled due to pressure increase of the pipe, then set the unit in cooling startup and fill
refrigerant from the low pressure check valve of the outdoor unit.
(3) Calculation example
Fig. 23
IDU:
No.
IDU
①
IDU
②
IDU
③
IDU
④
Model
Duct type
GMV-ND18PLS/A-
T(U)
Duct type
GMV-ND12PLS/A-T
(U)
Duct type
GMV-ND09PLS/A-T
(U)
Duct type
GMV-ND09PLS/A-T
(U)
Liquid pipe:
No.
A
B
C
D
Pipe size
Φ9.52mm
(
Φ3/8inch)
Φ9.52mm
(
Φ3/8inch)
Φ9.52mm
(
Φ3/8inch)
Φ6.35mm
(
Φ1/4inch)
Length
10m
(32-3/4feet)
5m
(16-3/8feet)
5m
(16-3/8feet)
5m
(16-3/8feet)
No.
a
b
c
d
Pipe size
Φ9.52mm
(
Φ3/8inch)
Φ6.35mm
(
Φ1/4inch)
Φ6.35mm
(
Φ1/4inch)
Φ6.35mm
(
Φ1/4inch)
Length
3m
(9-3/4feet)
3m
(9-3/4feet)
2m
(6-5/8feet)
1m
(3-1/4feet)
Total length of each liquid pipe
Φ9.52
:
A+B+C+a=10+5+5+3=23m(75-1/2 feet)
Φ6.35: D+b+c+d=5+3+2+1=11m(36feet)
NOTICE!
Liquid pipe that is within 20m(65-
5/8 feet) doesn’t need to be added with
refrigerant.
Therefore, the minimum quantity of additional refrigerant = (23-20)×0.054+11×0.022
=
0.404kg(14oz)
Summary of Contents for GMV-36WL/A-T(U)
Page 1: ...DC INVERTER SIDE DISCHARGE VRF Ⅱ FOR NORTH AMERICA ...
Page 3: ...DC Inverter Side Discharge VRF Ⅱ for North America 1 PRODUCT ...
Page 10: ...DC Inverter Side Discharge VRF Ⅱ for North America 8 CONTROL ...
Page 15: ...DC Inverter Side Discharge VRF Ⅱ for North America 13 ...
Page 16: ...DC Inverter Side Discharge VRF Ⅱ for North America 14 Button Graphics ...
Page 24: ...DC Inverter Side Discharge VRF Ⅱ for North America 22 4 3 2 2 Appearance ...
Page 30: ...DC Inverter Side Discharge VRF Ⅱ for North America 28 Installation is in progress ...
Page 33: ...DC Inverter Side Discharge VRF Ⅱ for North America 31 Installation is in progress ...
Page 35: ...DC Inverter Side Discharge VRF Ⅱ for North America 33 Click Next ...
Page 65: ...DC Inverter Side Discharge VRF Ⅱ for North America 63 Switchover of Software Languages ...
Page 66: ...DC Inverter Side Discharge VRF Ⅱ for North America 64 INSTALLATION ...
Page 94: ...DC Inverter Side Discharge VRF Ⅱ for North America 92 MAINTENANCE ...
Page 131: ...JF00302320 ...