DC Inverter Side Discharge VRF
Ⅱ
for North America
73
5.3 Selection of Indoor Branches
Select indoor branches according to the total capacity of downstream indoor units. if
the capacity exceeds that of the outdoor unit, capacity of outdoor unit prevails.
Refrigerant system
Total capacity of downstream indoor units C (Btu/h)
Model
Y type branch
C< 68200
FQ01A
68200
≤
C
≤
102400
FQ01B
102400
<
C
≤
238800
FQ02
238800
<
C
≤
460600
FQ03
460600
<
C
FQ04
5.4 Dimension of Pipe between Indoor Branches
Select pipe between indoor branches according to the capacity of downstream indoor
units; if the capacity exceeds that of the outdoor unit, capacity of outdoor unit prevails.
Summary of Contents for GMV-36WL/A-T(U)
Page 1: ...DC INVERTER SIDE DISCHARGE VRF Ⅱ FOR NORTH AMERICA ...
Page 3: ...DC Inverter Side Discharge VRF Ⅱ for North America 1 PRODUCT ...
Page 10: ...DC Inverter Side Discharge VRF Ⅱ for North America 8 CONTROL ...
Page 15: ...DC Inverter Side Discharge VRF Ⅱ for North America 13 ...
Page 16: ...DC Inverter Side Discharge VRF Ⅱ for North America 14 Button Graphics ...
Page 24: ...DC Inverter Side Discharge VRF Ⅱ for North America 22 4 3 2 2 Appearance ...
Page 30: ...DC Inverter Side Discharge VRF Ⅱ for North America 28 Installation is in progress ...
Page 33: ...DC Inverter Side Discharge VRF Ⅱ for North America 31 Installation is in progress ...
Page 35: ...DC Inverter Side Discharge VRF Ⅱ for North America 33 Click Next ...
Page 65: ...DC Inverter Side Discharge VRF Ⅱ for North America 63 Switchover of Software Languages ...
Page 66: ...DC Inverter Side Discharge VRF Ⅱ for North America 64 INSTALLATION ...
Page 94: ...DC Inverter Side Discharge VRF Ⅱ for North America 92 MAINTENANCE ...
Page 131: ...JF00302320 ...