DC Inverter Side Discharge VRF
Ⅱ
for North America
101
(11)
Desynchronizing protection for inverter compressor
LED3 dual-8
nixie tube
displays P9
Whether the
sequence of wire
for compressor is
correct?
yes
Replace the main
board. Work
normally?
no
Replace
compressor
Work normally
yes
Adjust the
sequence of wire
for compressor
Whether
the wiring terminal
for compressor is
loose?
Connect the wires
of compressor
tightly
yes
no
no
Wired
controller
displays P0
(12)
Failure startup for inverter compressor
Wired
controller
displays P0
LED3 dual-8
nixie tube
displays PJ
Replace main
board. Work
normally?
Replace
compressor
Work normally
yes
no
Summary of Contents for GMV-36WL/A-T(U)
Page 1: ...DC INVERTER SIDE DISCHARGE VRF Ⅱ FOR NORTH AMERICA ...
Page 3: ...DC Inverter Side Discharge VRF Ⅱ for North America 1 PRODUCT ...
Page 10: ...DC Inverter Side Discharge VRF Ⅱ for North America 8 CONTROL ...
Page 15: ...DC Inverter Side Discharge VRF Ⅱ for North America 13 ...
Page 16: ...DC Inverter Side Discharge VRF Ⅱ for North America 14 Button Graphics ...
Page 24: ...DC Inverter Side Discharge VRF Ⅱ for North America 22 4 3 2 2 Appearance ...
Page 30: ...DC Inverter Side Discharge VRF Ⅱ for North America 28 Installation is in progress ...
Page 33: ...DC Inverter Side Discharge VRF Ⅱ for North America 31 Installation is in progress ...
Page 35: ...DC Inverter Side Discharge VRF Ⅱ for North America 33 Click Next ...
Page 65: ...DC Inverter Side Discharge VRF Ⅱ for North America 63 Switchover of Software Languages ...
Page 66: ...DC Inverter Side Discharge VRF Ⅱ for North America 64 INSTALLATION ...
Page 94: ...DC Inverter Side Discharge VRF Ⅱ for North America 92 MAINTENANCE ...
Page 131: ...JF00302320 ...