DC Inverter Side Discharge VRF
Ⅱ
for North America
91
No.
Debug item
Parameter
name
Unit
Reference
7
System
parame
ters
ODU
parame
ters
Compressor’
s operating
freq
HZ
GMV-36WL/A-T(U)
GMV-48WL/A-T(U)
Changes in
10Hz~80Hz.
GMV-60WL/A-T(U)
Changes in
16Hz~80Hz
8
Compressor’
s operating
current
A
When compressor works normally, the current is no
more than22.6A.
9
Compressor’
s IPM temp
℃
(
℉
)
When ambient temp is below 35
℃
(95
℉
), IPM temp
is lower than 80
℃
(176
℉
) and the highest temp won’t
be above 95
℃
(203
℉
).
10
Fan motor’s
operating
freq
HZ
GMV-36WL/A-T(U)
GMV-48WL/A-T(U)
Changes in
0~49Hz
according to
system’s
pressure.
GMV-60WL/A-T(U)
Changes in
0~40Hz
according to
system’s
pressure.
11
IDU
parame
ters
IDU ambient
temp
℃
(
℉
)
——
12
Indoor heat
exchanger’s
inlet temp
℃
(
℉
)
According to ambient temp, for a same IDU in cool
mode, the inlet temp will be 1
℃
~7
℃
(34~45
℉
) lower
than the outlet temp, and 4~9
℃
(39~48
℉
) higher
than the low pressure value.
For a same IDU in heat mode, the inlet temp will be
10
℃
~20
℃
(50~68
℉
) lower than the outlet temp.
13
14
Opening
angle of
indoor EXV
PLS
GMV-36WL/A-T(U)
GMV-48WL/A-T(U)
In cool mode, the
opening angle of
indoor EXV
varies within
70~480PLS.
In heat mode,
the opening
angle of indoor
EXV varies
within
70~480PLS.
GMV-60WL/A-T(U)
In cool mode, the
opening angle of
indoor EXV
varies within
70~480PLS.
In heat mode,
the opening
angle of indoor
EXV varies
within
40~480PLS.
15
Communication
parameters
Communicati
on data
—
Number of IDUs detected by software is the same
with the actual number. No communication error.
16
Drainage system
——
—
Indoor unit can drain water out completely and
smoothly. Condensate pipe has no backward slope of
water; Water of outdoor unit can be drained
completely through drainage pipe. No water drop
from unit base.
17
Others
——
—
Compressor and indoor/outdoor fan motor do not
have strange noise. Unit can operate normally.
Summary of Contents for GMV-36WL/A-T(U)
Page 1: ...DC INVERTER SIDE DISCHARGE VRF Ⅱ FOR NORTH AMERICA ...
Page 3: ...DC Inverter Side Discharge VRF Ⅱ for North America 1 PRODUCT ...
Page 10: ...DC Inverter Side Discharge VRF Ⅱ for North America 8 CONTROL ...
Page 15: ...DC Inverter Side Discharge VRF Ⅱ for North America 13 ...
Page 16: ...DC Inverter Side Discharge VRF Ⅱ for North America 14 Button Graphics ...
Page 24: ...DC Inverter Side Discharge VRF Ⅱ for North America 22 4 3 2 2 Appearance ...
Page 30: ...DC Inverter Side Discharge VRF Ⅱ for North America 28 Installation is in progress ...
Page 33: ...DC Inverter Side Discharge VRF Ⅱ for North America 31 Installation is in progress ...
Page 35: ...DC Inverter Side Discharge VRF Ⅱ for North America 33 Click Next ...
Page 65: ...DC Inverter Side Discharge VRF Ⅱ for North America 63 Switchover of Software Languages ...
Page 66: ...DC Inverter Side Discharge VRF Ⅱ for North America 64 INSTALLATION ...
Page 94: ...DC Inverter Side Discharge VRF Ⅱ for North America 92 MAINTENANCE ...
Page 131: ...JF00302320 ...