DC Inverter Side Discharge VRF
Ⅱ
for North America
74
Total capacity of downstream indoor units
C (Btu/h)
Pipe
(mm/inch)
Liquid pipe
(mm/inch)
C ≤19000
Φ12.7
(
Φ1/2)
Φ6.35
(
Φ1/4)
19000<
C≤48500
Φ15.9
(
Φ5/8)
Φ9.52
(
Φ3/8)
48500<
C≤76400
Φ19.05
(
Φ3/4)
Φ9.52
(
Φ3/8)
5.5 Dimension of Pipe between Indoor Branch and IDU
Dimension of pipe between indoor branch and IDU should be consistent with the
dimension of indoor pipe.
Fig. 9
Rated capacity of IDU
C(Btu/h)
Gas pipe
(mm/inch)
Liquid pipe
(mm/inch)
C≤9600
Φ9.52
(
Φ3/8)
Φ6.35
(
Φ1/4)
9600<
C≤17000
Φ12.7
(
Φ1/2)
Φ6.35
(
Φ1/4)
17000<
C≤48000
Φ15.9
(
Φ5/8)
Φ9.52
(
Φ3/8)
48000<
C≤55000
Φ19.05
(
Φ3/4)
Φ9.52
(
Φ3/8)
55000<
C≤96000
Φ22.2
(
Φ7/8)
Φ9.52
(
Φ3/8)
NOTICE!
If the distance between IDU and its nearest branch is over 10m(33feet),
then the liquid pipe of IDU (rated capacity ≤17000Btu/h) shall be enlarged.
Summary of Contents for GMV-36WL/A-T(U)
Page 1: ...DC INVERTER SIDE DISCHARGE VRF Ⅱ FOR NORTH AMERICA ...
Page 3: ...DC Inverter Side Discharge VRF Ⅱ for North America 1 PRODUCT ...
Page 10: ...DC Inverter Side Discharge VRF Ⅱ for North America 8 CONTROL ...
Page 15: ...DC Inverter Side Discharge VRF Ⅱ for North America 13 ...
Page 16: ...DC Inverter Side Discharge VRF Ⅱ for North America 14 Button Graphics ...
Page 24: ...DC Inverter Side Discharge VRF Ⅱ for North America 22 4 3 2 2 Appearance ...
Page 30: ...DC Inverter Side Discharge VRF Ⅱ for North America 28 Installation is in progress ...
Page 33: ...DC Inverter Side Discharge VRF Ⅱ for North America 31 Installation is in progress ...
Page 35: ...DC Inverter Side Discharge VRF Ⅱ for North America 33 Click Next ...
Page 65: ...DC Inverter Side Discharge VRF Ⅱ for North America 63 Switchover of Software Languages ...
Page 66: ...DC Inverter Side Discharge VRF Ⅱ for North America 64 INSTALLATION ...
Page 94: ...DC Inverter Side Discharge VRF Ⅱ for North America 92 MAINTENANCE ...
Page 131: ...JF00302320 ...