DC Inverter Side Discharge VRF
Ⅱ
for North America
60
(2)
Usage of converter configuring software:
When the converter is working, hold the button ”SET” for 5 sec. Function LED will be
flickering, indicating that the converter has enter the baud rate setting mode. Then
you can use the converter configuring software to set the baud rate of converter.
Baud rate
supported by the converter (baud rate of air conditioner’s communication
interface matches with the baud rate of USB interface automatically):
Ex-factory defaulted baud rate: (unit: bps)
AC is connected with
Baud rate of air conditioner interface
Baud rate of USB interface
CAN
20000/50000 self-adaptive
115200
HBS
57600
38400
RS485
9600
9600
Baud rate look-up table for RS485 interface (unit: bps)
RS485 interface
4800
9600
19200
38400
57600
115200
USB interface
4800
9600
19200
38400
57600
115200
Baud rate look-up table for HBS interface (unit: bps)
HBS interface
9600
19200
38400
57600
USB interface
4800
9600
19200
38400
Baud rate look-up table of CAN interface (unit: bps)
Double-click the desktop shortcut.
CAN interface
20000
50000
100000
125000
USB interface
115200
115200
256000
256000
Summary of Contents for GMV-36WL/A-T(U)
Page 1: ...DC INVERTER SIDE DISCHARGE VRF Ⅱ FOR NORTH AMERICA ...
Page 3: ...DC Inverter Side Discharge VRF Ⅱ for North America 1 PRODUCT ...
Page 10: ...DC Inverter Side Discharge VRF Ⅱ for North America 8 CONTROL ...
Page 15: ...DC Inverter Side Discharge VRF Ⅱ for North America 13 ...
Page 16: ...DC Inverter Side Discharge VRF Ⅱ for North America 14 Button Graphics ...
Page 24: ...DC Inverter Side Discharge VRF Ⅱ for North America 22 4 3 2 2 Appearance ...
Page 30: ...DC Inverter Side Discharge VRF Ⅱ for North America 28 Installation is in progress ...
Page 33: ...DC Inverter Side Discharge VRF Ⅱ for North America 31 Installation is in progress ...
Page 35: ...DC Inverter Side Discharge VRF Ⅱ for North America 33 Click Next ...
Page 65: ...DC Inverter Side Discharge VRF Ⅱ for North America 63 Switchover of Software Languages ...
Page 66: ...DC Inverter Side Discharge VRF Ⅱ for North America 64 INSTALLATION ...
Page 94: ...DC Inverter Side Discharge VRF Ⅱ for North America 92 MAINTENANCE ...
Page 131: ...JF00302320 ...